Sentinel Kinetic MVHR with Cooker Hood Installation & Commissioning
Installation
Overview
The following instructions are intended to help prevent potential hazards and should be carried out only by a
qualified electrician and installer.
Before Installing the Unit
Inspect the Unit
When taking delivery of the unit, check the items delivered against the delivery note. Inspect the unit for
damage in transit. If in doubt, contact Customer Services. The Sentinel Kinetic with cooker hood is made up of
two separate boxes. Each box containing the Sentinel Kinetic HR with metal duct assembly should come with
an accessory pack containing wall brackets, condensate drain link pipes, worm-drive clips, fixings and product
documentation. Each box containing the cooker hood should contain an accessory pack consisting of black
protective box for cooker hood socket and plug connection, screws, cable receptors and product documentation.
A template to aid marking out the wall for drilling is printed on the carton.
Lift and Move the Unit Safely
The weight of this unit is 28 kg. Always use appropriate lifting techniques and appliances when moving heavy
equipment.
Check Site Requirements and Safety Notices
Check that the physical and environmental conditions for the site meet, or exceed, the requirements detailed in
the Technical Specification on page 6.
Read and observe the safety notices listed in IMPORTANT on page 2.
Unit Installation
READ THE SENTINEL KINETIC INSTALLATION & COMMISSIOING DOCUMENT BEFORE INSTALLING
THIS UNIT. In particular, ensure that any external switches, sensors and electrical connections are made prior
to the unit being mounted on the wall.
The Sentinel Kinetic Cooker Hood is only suitable for installation above a domestic cooker or cooker hob. The
unit with cooker hood must be sited a minimum of 650mm above an electric hob and 750mm above a
gas hob.
It will fit in a 600 mm (external) x 300 mm deep (internal) kitchen wall cupboard space above the hob.
The wall should have sufficient strength to support the unit.
Take into consideration the position of the electrical services and the condensate drain.
Ensure there is adequate access for installation, operation and maintenance.
It is recommended that a local mains and sensor terminal connection box is installed within 1m of the unit to
facilitate future maintenance, rather than wiring these directly to the unit.
The unit MUST always be mounted vertically with ducting exiting vertically. Do not use this unit as a support for
any other equipment.
Select Unit Orientation
The unit may be purchased as left or right hand, where left hand refers to the connections to atmosphere being
on the left side of the unit.