Table 4.4: P0695 parameter bit functions
Bits
Values
Bit 0
DO1 setting
0: DO1 output open.
1: DO1 output closed.
Bit 1
DO2 setting
0: DO2 output open.
1: DO2 output closed.
Bit 2
DO3 setting
0: DO3 output open.
1: DO3 output closed.
Bit 3
DO4 setting
0: DO4 output open.
1: DO4 output closed.
Bit 4
DO5 setting
0: DO5 output open.
1: DO5 output closed.
Bits 5 to 15
Reserved
NOTE!
Some of the digital outputs may not be available depending on the plug-in module.
P0696 – VALUE 1 FOR ANALOG OUTPUTS
P0697 – VALUE 2 FOR ANALOG OUTPUTS
P0698 – VALUE 3 FOR ANALOG OUTPUTS
Range:
-32768 to 32767
Default: 0
Properties:
-
Access groups via HMI:
NET
Description:
They allow the control of the analog outputs by means of network interfaces (Serial, CAN, etc.). These
parameters cannot be changed via HMI.
The value written in these parameters is used as the analog output value, providing that the function for the
desired analog output be programmed for “P0696 / P0697 / P0698 value”, at the parameters P0251, P0254,
P0257.
The value must be written in a 15-bit scale (7FFFh = 32767)
2
to represent 100 % of the output desired
value, i.e.:
P0696 = 0000h (0 decimal)
→ analog output value = 0 %
P0696 = 7FFFh (32767 decimal)
→ analog output value = 100 %
The showed example was for P0696, but the same scale is also used for the parameters P0697 / P0698. For
instance, to control the analog output 1 via serial, the following programming must be done:
Choose a parameter from P0696, P0697, P0698 to be the value used by the analog output 1. For this
example, we are going to select P0696.
Program the option “P0696 value” as the function for the analog output 1 in P0254.
Using the network interface, write in P0696 the desired value for the analog output 1, between 0 and 100
%, according to the parameter scale.
NOTE!
For CFW500 frequency inverter, the analog output 3 represents the frequency output (FO).