3 INSTALLATION IN THE PROFIBUS DP NETWORK
The Profibus DP network, such as several industrial communication networks, for being many times applied in
aggressive environments with high exposure to electromagnetic interference, requires that certain precautions
be taken in order to guarantee a low communication error rate during its operation. Recommendations to
perform the product connection in this network are presented next.
3.1 BAUD RATES
The Profibus DP protocol defines several baud rates that can be used, from 9.6 kbit/s up to 12Mbit/s. The
maximum allowed transmission line length depends on the used baud rate, and this correlation is showed on
the table 3.1.
Table 3.1: Baud rate x segment length
Baud Rate
(kbit/s)
Segment Length
(m)
9,6; 19,2; 45,45; 93,75
1200
187,5
1000
500
400
1500
200
3000, 6000, 12000
100
All equipments in the network must use the same baud rate. The CFW500 Profibus DP interface has automatic
baud rate detection, according to what has been configured for the network master, and therefore it is not
necessary to configure this option.
It is possible to observe the baud rate detected by the board at the parameter P0963.
3.2 ADDRESSING
Every device in a Profibus DP network, master or slave, is identified through a network address. This address
must be different for each device.
The CFW500 Profibus DP address is configured through the parameter P0918.
3.3 CABLE
It is recommended that the installation be carried out with a type A cable, whose characteristics are described in
the table 3.2. The cable has a pair of wires that must be shielded and twisted, in order to guarantee higher
immunity against electromagnetic interference.
Table 3.2: Type A cable properties
Impedance
135 a 165 Ω
Capacitance
30 pf/m
Loop resistance
110 Ω/km
Cable diameter
> 0.64 mm
Wire cross section
> 0.34 mm
3.4 CONNECTORS
Several connector types can be used for the network connection of the equipment, from simple screw
connectors up to very specific connector types for the Profibus network.
The connector used in the CFW500 Profibus DP accessory is presented at item 3.4.
3.5 CONNECTION TO THE NETWORK
The Profibus DP protocol, by using the RS-485 physical medium, allows the connection of up to 32 devices per
segment without the use of repeaters. By using repeaters, up to 126 addressable equipments can be