Xeoos Twinfire Basic Operating And Installation Instructions - page 6
6
Each chimney connector or chimney connector section must
be installed to the stove flue collar and to each other with the
male (crimped) end toward the stove. This prevents any
amount of condensed or liquid creosote from running down the
outside of the pipe or the stove top. The flue collar connector
should be secured with approved fasteners to ensure that the
sections do not separate. For the best performance the
chimney connector should be as short and direct as possible,
with no more than two 90° elbows.
DO NOT CONNECT THIS STOVE TO ANOTHER CHIMNEY FLUE OR AIR
DISTRIBUTION DUCT OR ANY SYSTEM SERVING ANOTHER APPLIANCE.
For venting vertically into a masonry chimney, single wall stainless steel (at least 24 gauge and
6” in diameter) must be used in the room where the stove is installed. Refer to the manufactur-
er’s instructions for the connection to the listed chimney.
RURAL ONLY. For rear venting or other not listed configurations, consult the local building
codes.
If the chimney connector is fitted with a
baffle, it must be manually operated, visi-
bly placed for ease of use, and must not
close completely. Consult your chimney
expert if you have any questions. Make
sure that there is easy access to the
Chimney
Flue
Masonry
Min.
2”(5cm)
Connector Pipe
18”(46cm)
below
ceiling
chimney cleanout door. Floor protection is
required under the chimney connector and
2" (51cm) beyond each side. Baffles
should only be fitted to fix situations
relating to over drawing.
Insulated
Chimney
Min.
2”(5cm)