ABB i-bus KNX FCL/S 1.6.1.1 Product Manual - page 37
Manual is about: Blower Actuator, FCL/S x.6.1.1 Series
of
104
ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 35
Send object value "Fault control value"
Options:
No, update only
Only after changing
After request
After a change or request
No, update only
: The status is updated but not sent.
Only after changing
: The status is sent after a change.
After request
: The status is sent after a request.
After a change or request
: The status is sent after a change or a request.
Set control value during fault
Options:
No
Yes
This parameter sets how the output reacts in the event of an error.
Yes
: The following parameter appears:
Control value in % [0...100]
Options:
0...30...100
This parameter sets what percentage to use for the control value in the event of an error.