Start-up
42 2CDC508116D0203 | FCL/S x.6.1.1
Run-on behavior
Options:
No
Yes
This parameter activates a run-on for the fan. If the fan changes to a lower speed, it remains in the previ-
ous speed for as long as the parameterized run-on time and only then reduces the speed.
If the fan goes through several speed changes, run-on times are executed successively, adding on those
times.
A run-on time of 0 seconds means that run-on is deactivated.
Run-on is executed regardless of where the speed change originates (automatic operation, direct opera-
tion, manual procedure, fan switch off).
Yes
: The following parameters appear:
Run-on stage 3 in s [0...65,535]
Options:
0...20...65,535
Run-on stage 2 in s [0...65,535]
Options:
0...20...65,535
Run-on stage 1 in s [0...65,535]
Options:
0...20...65,535
The parameterized run-on times can be switched on or off with the
Run-on
communication object.