ABB i-bus KNX FCL/S 1.6.1.1 Product Manual - page 62
ABB i-bus
®
KNX
Start-up
60 2CDC508116D0203 | FCL/S x.6.1.1
Restart of staircase time after end
of permanent ON
Options:
No
Yes
No
: The lighting switches off if
Permanent ON
is ended.
Yes
: The lighting remains on and the staircase lighting time restarts.
The function of Permanent ON is controlled via the
Permanent ON
communication object value. If
the communication object receives a telegram with the value 1, the output is switched on regardless
of the value of the communication object
Switch
and remains switched on until the communication
object
Permanent ON
has the value 0.
Object value "Disable function Time"
after a download
Options:
Unchanged
1 = disable function Time
0 = enable function Time
Unchanged
: After a download, the communication object has the same value as before.
1 = disable function Time
: The
Time
function is disabled by a telegram with the value 1.
0 = disable function Time
: The
Time
function is disabled by a telegram with the value 0.