ABB i-bus KNX FCL/S 1.6.1.1 Product Manual - page 54
ABB i-bus
®
KNX
Start-up
52 2CDC508116D0203 | FCL/S x.6.1.1
Where there are two control value inputs, the following additional parameter appears:
Function of monitoring
Options:
Monitoring current control values
Monitoring active and inactive control values
This parameter determines the scope of monitoring.
Monitoring current control values
: Only the currently selected control value input is monitored
for incoming telegram continuity. After a switchover (via C
ommunication object "Control value
A/B
" or
Largest value
), monitoring restarts.
Monitoring active and inactive control values
: Both control value inputs are always monitored
independently of each other. An error is reported if an object's time is exceeded.
Send object value "Fault control value"
Options:
No, update only
Only after changing
After request
After a change or request
No, update only
: The status is updated but not sent.
Only after changing
: The status is sent after a change.
After request
: The status is sent after a request.
After a change or request
: The status is sent after a change or a request.
Set control value during fault
Options:
No
Yes
This parameter sets the reaction in the event of an error.
Yes
: The following parameter appears:
Control value in % [0...100]
Options:
0...30...100
This parameter sets what percentage to use for the control value in the event of an error.