- DL manuals
- ABB
- Relays
- rec670
- Product Manual
ABB rec670 Product Manual - page 107
SEMOD141136-2 v8
Table 154. IRIG-B
Quantity
Rated value
Number of channels IRIG-B
1
Number of optical channels
1
Electrical connector:
Electrical connector IRIG-B
BNC
Pulse-width modulated
5 Vpp
Amplitude modulated
– low level
– high level
1-3 Vpp
3 x low level, max 9 Vpp
Supported formats
IRIG-B 00x, IRIG-B 12x
Accuracy
+/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Input impedance
100 k ohm
Optical connector:
Optical connector IRIG-B
Type ST
Type of fibre
62.5/125 μm multimode fibre
Supported formats
IRIG-B 00x
Accuracy
+/- 1μs
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB
107
Summary of rec670
Page 1
Relion® 670 series — bay control rec670 version 2.2 product guide.
Page 2
Contents 1. Application..................................................................... 3 2. Available functions..........................................................9 3. Control......................................................................... 25 4. Differential protection.............
Page 3
1. Application m13637-3 v13 the intelligent electronic device (ied) is used for the control, protection and monitoring of different types of bays in power networks. The ied is especially suitable for applications in control systems where the iec 61850–8–1 ed 1 or ed 2 station bus features of the ied...
Page 4
Description of configuration a30 m15200-3 v7 rec670 a30 – double busbar in single breaker arrangement 12ai (6i + 6u) qb1 qa1 qb2 qb9 s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 contr...
Page 5
Description of configuration b30 m15200-12 v5 rec670 b30 - double breaker arrangement 12ai (6i + 6u) qb1 qa1 qb61 qb2 qa2 qb62 qb9 s cilo 3 control s cswi 3 control s xcbr 3 control etp mmtr met w/varh brc ptoc 46 iub> cc psdc 52pd pd other functions available from the function library lov ptuv 27 3...
Page 6
Description of configuration c30 m15200-24 v5 s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control...
Page 7
Description of configuration d30 guid-15d86a4c-4d37-432e-8dc2-518814830097 v1 rec670 d30 – double busbar in single breaker arrangement with pmu functionality 12ai (6i + 6u) qb1 qa1 qb2 qb9 s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 ...
Page 8
The basic delivery includes one binary input module and one binary output module, which is sufficient for the default configured io to trip and close circuit breaker. All ieds can be reconfigured with the help of the application configuration tool in pcm600. The ied can be adapted to special applica...
Page 9
2. Available functions guid-f5776dd1-bd04-4872-bb89-a0412b4b5cc3 v1 the following tables list all the functions available in the ied. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. Main protection functions guid-66baad98-851d-4aac-b...
Page 10
Back-up protection functions guid-a8d0852f-807f-4442-8730-e44808e194f0 v13 iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) current protection phpioc 50 instantaneous phase overcurrent protection 0-6 1-c51 2-c52 ...
Page 11
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) saptuf 81 underfrequency protection 0-6 6-e01 6-e01 6-e01 6-e01 saptof 81 overfrequency protection 0-6 6-e01 6-e01 6-e01 6-e01 sapfrc 81 rate-of-change of frequenc...
Page 12
Control and monitoring functions guid-e3777f16-0b76-4157-a3bf-0b6b978863de v15 iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) control sesrsyn 25 synchrocheck, energizing check and synchronizing 0-6 1 2 3 1 smbr...
Page 13
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) ccsspvc 87 current circuit supervision 0-6 1 2 3 1 fufspvc fuse failure supervision 0-4 3 3 3 3 vdspvc 60 fuse failure supervision based on voltage difference 0-2 ...
Page 14
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) teigapc elapsed time integrator with limit transgression and overflow supervision 12 12 12 12 12 intcomp comparator for integer inputs 30 30 30 30 30 realcomp comp...
Page 15
Table 3. Number of function instances in apc10 function name function description total number of instances scilo interlocking 10 bb_es 3 a1a2_bs 2 a1a2_dc 3 abc_bc 1 bh_conn 1 bh_line_a 1 bh_line_b 1 db_bus_a 1 db_bus_b 1 db_line 1 abc_line 1 ab_trafo 1 scswi switch controller 10 sxswi circuit swit...
Page 16
Table 4. Number of function instances in apc15 function name function description total number of instances scilo interlocking 15 bb_es 3 a1a2_bs 2 a1a2_dc 3 abc_bc 1 bh_conn 1 bh_line_a 1 bh_line_b 1 db_bus_a 1 db_bus_b 1 db_line 1 abc_line 1 ab_trafo 1 scswi switch controller 15 sxswi circuit swit...
Page 17
Table 5. Number of function instances in apc30 function name function description total number of instances scilo interlocking 30 bb_es 6 a1a2_bs 4 a1a2_dc 6 abc_bc 2 bh_conn 2 bh_line_a 2 bh_line_b 2 db_bus_a 3 db_bus_b 3 db_line 3 abc_line 6 ab_trafo 4 scswi switch controller 30 sxswi circuit swit...
Page 18
Table 7. Total number of instances for extended logic package extended configurable logic block total number of instances and 180 gate 49 inv 180 lld 49 or 180 pulsetimer 89 rsmemory 40 slgapc 74 srmemory 130 timerset 109 vsgapc 120 xor 89 1mrk 511 404-ben a bay control rec670 2.2 product version: 2...
Page 19
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) monitoring cvmmxn power system measurement 6 6 6 6 6 cmmxu current measurement 10 10 10 10 10 vmmxu voltage measurement phase-phase 6 6 6 6 6 cmsqi current sequenc...
Page 20
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) metering pcfcnt pulse-counter logic 16 16 16 16 16 etpmmtr function for energy calculation and demand handling 6 6 6 6 6 1mrk 511 404-ben a bay control rec670 2.2 ...
Page 21
Communication guid-5f144b53-b9a7-4173-80cf-cd4c84579cb5 v15 iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) station communication lonspa, spa spa communication protocol 1 1 1 1 1 ade lon communication protocol 1...
Page 22
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) optical103 iec 60870-5-103 optical serial communication 1 1 1 1 1 rs485103 iec 60870-5-103 serial communication for rs485 1 1 1 1 1 agsal generic security applicat...
Page 23
Iec 61850 or function name ansi function description bay control rec670 (customized) rec670 (a30) rec670 (b30) rec670 (c30) rec670 (d30) binsigntrans1_1 binsigntrans1_2 binsigntransm2 binary signal transfer transmit 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 binsigrec1_12m binsigrec1_22m binsigtran1_12m binsigtr...
Page 24
Basic ied functions guid-c8f0e5d2-e305-4184-9627-f6b5864216ca v12 table 9. Basic ied functions iec 61850 or function name description interrsig self supervision with internal event list timesynchgen time synchronization module bininput, synchcan, synchgps, synchcmpps, synchlon, synchpph, synchpps, s...
Page 25
Table 10. Local hmi functions iec 61850 or function name ansi description lhmictrl local hmi signals language local human machine language screen local hmi local human machine screen behavior fnkeyty1–fnkeyty5 fnkeymd1– fnkeymd5 parameter setting function for hmi in pcm600 ledgen general led indicat...
Page 26
• substitution of position and quality indications • overriding of interlocking functions • overriding of synchrocheck • operation counter • suppression of mid position two types of command models can be used: • direct with normal security • sbo (select-before-operate) with enhanced security normal ...
Page 27
Reservation input resin m16501-3 v5 the reservation input (resin) function receives the reservation information from other bays. The number of instances is the same as the number of involved bays (up to 60 instances are available). Bay control qcbay m13447-3 v8 the bay control (qcbay) function is us...
Page 28
Plays the same role as functions goosebinrcv (for iec 61850) and multicmdrcv (for lon). Single command, 16 signals m12446-6 v5 the ieds can receive commands either from a substation automation system or from the local hmi. The command function block has outputs that can be used, for example, to cont...
Page 29
Instantaneous residual overcurrent protection efpioc m12701-3 v16 the instantaneous residual overcurrent protection (efpioc) has a low transient overreach and short tripping times to allow the use for instantaneous earth-fault protection, with the reach limited to less than the typical eighty percen...
Page 30
The thermal overload protection estimates the internal heat content of the transformer (temperature) continuously. This estimation is made by using a thermal model of the transformer with two time constants, which is based on current measurement. Two warning levels are available. This enables action...
Page 31
Prepare for system restoration at power outages or as a long- time delayed back-up to the primary protection. Uv2ptuv has two voltage steps, each with inverse or definite time delay. It has a high reset ratio to allow settings close to the system service voltage. Two step overvoltage protection ov2p...
Page 32
Start signal triggers the individual event timer, which is the continuous time spent within the given frequency band, and the accumulation timer, which is the cumulative time spent within the given frequency band. Once the timers reach their limit, an alarm or trip signal is activated to protect the...
Page 33
12. Scheme communication scheme communication logic with delta based blocking scheme signal transmit zcpsch m13860-3 v10 to achieve instantaneous fault clearance for all line faults, scheme communication logic is provided. All types of communication schemes for permissive underreaching, permissive o...
Page 34
The trip function can collect start and directional signals from different application functions. The aggregated start and directional signals are mapped to the iec 61850 logical node data model. General start matrix block smagapc guid-ba516165-96de-4cd9-979b-29457c7653c0 v3 the start matrix (smagap...
Page 35
• indextspqt extracts individual signals from a group signal input. The value part of single position input is copied to si_out output. The time part of single position input is copied to time output. The quality bits in the common part and the indication part of inputs signal are copied to the corr...
Page 36
Value. It is a basic arithmetic function that can be used for monitoring, supervision, interlocking and other logics. 14. Monitoring measurements cvmmxn, cmmxu, vnmmxu, vmmxu, cmsqi, vmsqi m12024-3 v9 the measurement functions are used to get on-line information from the ied. These service values ma...
Page 37
The event recording information is an integrated part of the disturbance record (comtrade file). Trip value recorder drprdre m12128-3 v7 information about the pre-fault and fault values for currents and voltages are vital for the disturbance evaluation. The trip value recorder calculates the values ...
Page 38
The fault locator is an impedance measuring function giving the distance to the fault in km, miles or % of line length. The main advantage is the high accuracy achieved by compensating for load current and for the mutual zero- sequence effect on double circuit lines. The compensation includes settin...
Page 39
The values of active and reactive energies are calculated from the input power values by integrating them over a selected time tenergy . The integration of active and reactive energy values will happen in both forward and reverse directions. These energy values are available as output signals and al...
Page 40
Dhcp is available for the front port, and a device connected to it can thereby obtain an automatically assigned ip-address. Access points diagnostics guid-20f64a6d-aa8c-47d7-aa7d-4810996b2ff2 v1 the access point diagnostics function blocks (rchlcch, schlcch and frontstatus) supervise communication. ...
Page 41
Iec 60870-5-103 communication protocol semod120137-5 v4 a single glass or plastic port is provided for the iec 60870-5-103 standard. This allows design of simple substation automation systems including equipment from different vendors. Disturbance files uploading is provided. Measurands for iec 6087...
Page 42
Multiple command and transmit m14791-3 v3 when ieds are used in substation automation systems with lon, spa or iec 60870-5-103 communication protocols, the event and multiple command function blocks are used as the communication interface for vertical communication to station hmi and gateway, and as...
Page 43
Serial and lon communication module (slm) for spa/iec 60870-5-103, lon and dnp 3.0 m14933-3 v5 the serial and lon communication module (slm) is used for spa, iec 60870-5-103, dnp3 and lon communication. Slm has two optical communication ports for plastic/plastic, plastic/glass or glass/glass fibre c...
Page 44
Iec06000182-2-en.Vsd iec06000182 v2 en-us figure 10. A 1/2 x 19” size ied side-by-side with rhgs6. M15243-12 v9 case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242.1/ 9.53 255.8/ 10.07 205.7/ 8.10 190.5/ 7.50 203.7/ 8.02 - 228.6/ 9.00 - 6u, 3/4 x 19” 265.9/ 10.47 3...
Page 45
22. Connection diagrams guid-cf4effa5-3081-4fc7-9a14-ed127c3c0fde v6 the connection diagrams are delivered in the ied connectivity package as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/protection-control . Connection diagram...
Page 46
23. Technical data general ip11376-1 v2 m10993-1 v3 definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the ...
Page 47
Energizing quantities, rated values and limits analog inputs ip15842-1 v1 m16988-1 v11 table 11. Trm - energizing quantities, rated values and limits for protection transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1 or 5 ...
Page 48
Table 12. Trm - energizing quantities, rated values and limits for measuring transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1a 5 a operating range (0-1.8) × i r (0-1.6) × i r thermal withstand 80 × i r for 1 s 25 × i r ...
Page 49
Table 15. Sfp - galvanic rj45 quantity rated value number of channels up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol standard ieee 802.3u 100base-tx type of cable cat5e ftp table 15. Sfp - galvanic rj45, continued quantity rated valu...
Page 50
Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M50609-2 v7 table 18. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 22...
Page 51
Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M12318-1 v8 table 20. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) ...
Page 52
Bom/iom/som should be activated continuously due to power dissipation. M12584-1 v7 table 21. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max s...
Page 53
Bom/iom/som should be activated continuously due to power dissipation. Semod175395-2 v7 table 22. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48-60 vdc 110-250 vdc number of outputs 6 6 impedance ope...
Page 54
Table 23. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250 v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000 v rms current carrying capacity: continuous 8 a 1.0...
Page 55
Table 26. Auxiliary dc supply voltage influence on functionality during operation dependence on reference value within nominal range influence ripple, in dc auxiliary voltage operative range max. 2% full wave rectified 15% of el 0.01%/% auxiliary voltage dependence, operate value ±20% of el 0.01%/% ...
Page 56
Table 28. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-26 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12, class iv surge withstand capabilit...
Page 57
Table 30. Environmental tests test type test value reference standard cold operation test test ad for 16 h at -25°c iec 60068-2-1 cold storage test test ab for 16 h at -40°c iec 60068-2-1 dry heat operation test test bd for 16 h at +70°c iec 60068-2-2 dry heat storage test test bb for 16 h at +85°c ...
Page 58
Differential protection m13081-1 v12 table 33. High impedance differential protection, single phase hzpdif function range or value accuracy operate voltage (10-900) v i=u/r ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio >95% at (30-900) v - maximum continuous power u>trip 2 /seriesresisto...
Page 59
Wide area measurement system guid-f0baebd8-e361-4d50-9737-7df8b043d66a v4 table 34. Protocol reporting via ieee 1344 and c37.118 pmureport influencing quantity range accuracy signal frequency ± 0.1 x f r ≤ 1.0% tve signal magnitude: voltage phasor current phasor (0.1–1.2) x u r (0.5–2.0) x i r phase...
Page 60
Current protection m12336-1 v13 table 35. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of ibase - operate time at 0 to 2 x i set min. = 15 ms max. ...
Page 61
M12342-1 v20 table 36. Directional phase overcurrent protection, four steps oc4ptoc function setting range accuracy operate current, step 1-4 (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - minimum operate current, step 1-4 (1-10000)% of ...
Page 62
M15223-1 v17 table 38. Directional residual overcurrent protection, four steps ef4ptoc function range or value accuracy operate current, step 1-4 (1-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - relay characteristic angle (rca) (-180 to 180)...
Page 63
Guid-e83ad807-8fe0-4244-a50e-86b9af92469e v6 table 39. Four step directional negative phase sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase -...
Page 64
Semod173350-2 v16 table 40. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cosj directional residual overcurrent (0.25-200.00)% of ibase ±1.0% of i r at i £ i r ±1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cosj ...
Page 65
M12352-1 v14 table 41. Thermal overload protection, one time constant lcpttr/lfpttr function range or value accuracy reference current (2-400)% of ibase ±1.0% of i r reference temperature (0-300)°c, (0 - 600)°f ± 1.0°c, ±2.0°f operate time: 2 2 2 2 2 ln p trip amb p ref ref i i t t t i i i t t - = -...
Page 66
M12353-1 v14 table 43. Breaker failure protection ccrbrf function range or value accuracy operate phase current (5-200)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r ...
Page 67
Semod175152-2 v11 table 46. Directional underpower protection guppdup function range or value accuracy power level for step 1 and step 2 (0.0–500.0)% of sbase ±1.0% of s r at s ≤ s r ±1.0% of s at s > s r where 1.732 r r r s u i = × × characteristic angle for step 1 and step 2 (-180.0–180.0) degrees...
Page 68
Guid-6a7da510-e145-4c5b-a7dc-97bc4258e621 v9 table 49. Capacitor bank protection cbpgapc function range or value accuracy operate value, overcurrent (10-900)% of lbase ±2.0% of i r at i ≤ i r ±2.0% of i at i > i r reset ratio, overcurrent >95% at (100-900)% of ibase - start time, overcurrent, at 0.5...
Page 69
Guid-7ea9731a-8d56-4689-9072-d72d9cdfd795 v8 table 50. Voltage-restrained time overcurrent protection vrpvoc function range or value accuracy start overcurrent (2.0 - 5000.0)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent > 95% - operate time, start overcurrent at 0...
Page 70
Voltage protection m13290-1 v15 table 51. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ...
Page 71
M13304-1 v14 table 52. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time charac...
Page 72
M13317-2 v14 table 53. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 - step 2 (1.0-200.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r in...
Page 73
Semod175210-2 v6 table 55. Loss of voltage check lovptuv function range or value accuracy operate voltage (1–100)% of ubase ±0.5% of u r pulse timer when disconnecting all three phases (0.050–60.000) s ±0.2% or ±15 ms whichever is greater time delay for enabling the functions after restoration (0.00...
Page 74
Frequency protection m13360-1 v15 table 56. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ±2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms f...
Page 75
M14976-1 v9 table 58. Rate-of-change of frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever...
Page 76
Multipurpose protection m13095-2 v8 1mrk 511 404-ben a bay control rec670 2.2 product version: 2.2.1 76 abb.
Page 77
Table 60. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, - negseq, -3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2-phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph- ph - measuring voltage input...
Page 78
Table 60. General current and voltage protection cvgapc , continued function range or value accuracy independent time delay, overvoltage at 0.8 x u set to 1.2 x u set , step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater independent time delay, undervoltage at 1.2 x u set to 0.8 x u s...
Page 79
Table 60. General current and voltage protection cvgapc , continued function range or value accuracy undervoltage: critical impulse time 10 ms typically at 1.2 x u set to 0.8 x u set - impulse margin time 15 ms typically - 1mrk 511 404-ben a bay control rec670 2.2 product version: 2.2.1 abb 79.
Page 80
Secondary system supervision m12358-1 v10 table 61. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0%...
Page 81
Guid-e2ea8017-bb4b-48b0-beda-e71fee353774 v5 table 63. Fuse failure supervision vdspvc function range or value accuracy operate value, block of main fuse failure (10.0-80.0)% of ubase ±0.5% of ur reset ratio operate time, block of main fuse failure at 1 x u r to 0 min. = 5 ms – max. = 15 ms reset ti...
Page 82
Control m12359-1 v15 table 64. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r rese...
Page 83
M12379-1 v13 table 65. Autorecloser smbrrec function range or value accuracy dead time: shot 1 “t1 1ph” shot 1 “t1 2ph” shot 1 “t1 3ph “ shot 1 “t1 3phhs” (0.000-120.000) s ±0.2% or ±35 ms whichever is greater dead time: shot 2 “t2 3ph” shot 3 “t3 3ph” shot 4 “t4 3ph” shot 5 “t5 3ph” (0.00-6000.00) ...
Page 84
Semod175215-2 v14 table 66. Voltage control tr1atcc/tr8atcc , tcmyltc/tclyltc function range or value accuracy transformer reactance (0.1–200.0) Ω, primary - time delay for lower command when fast step down mode is activated (1.0–100.0) s - voltage control set voltage (85.0–120.0)% of ubase ±0.25% o...
Page 85
Table 66. Voltage control tr1atcc/tr8atcc , tcmyltc/tclyltc , continued function range or value accuracy time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms whichever is greater tap changer constant time-out (1–120) s ±0.2% or ±200 ms whichever is greater raise/lower co...
Page 86
Scheme communication m16038-1 v14 table 67. Scheme communication logic with delta based blocking scheme signal transmit zcpsch function range or value accuracy scheme type off intertrip permissive ur permissive or blocking deltablocking - operate voltage, delta u (0–100)% of ubase ±5.0% of Δu operat...
Page 87
Guid-cc9a02c2-aae8-4b8c-a091-d4ed584a2ea7 v1 table 70. Local acceleration logic zclcpsch function range or value accuracy operate current, loadcurr (1–100)% of ibase ±1.0% of i r operate current, mincurr (1–100)% of ibase ±1.0% of i r delay time on pick-up for current release (0.000–60.000) s ±0.2% ...
Page 88
Logic m12380-1 v12 table 72. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolv...
Page 89
Guid-d1179280-1d99-4a66-91ac-b7343dba9f23 v2 table 79. Number of and instances logic block quantity with cycle time 3 ms 8 ms 100 ms and 60 60 160 guid-45df373f-dc39-4e1b-b45b-6b454e8e0e50 v2 table 80. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 10 10 20 guid-...
Page 90
Guid-c6c98fe0-f559-45ee-b853-464516775417 v2 table 87. Number of timerset instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms timerset 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms guid-0b07f78c-10bd-4070-aff0-6ee36454aa03 v1 table 88. Number of xor instances logic bl...
Page 91
Guid-61263951-53a8-4113-82b5-3db3bf0d9449 v1 table 95. Number of pulsetimerqt instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms pulsetimerqt - 10 30 (0.000–90000.000) s ±0.5% ±10 ms guid-94c803b4-6c5a-4072-ab5c-20dde98c9a70 v1 table 96. Number of rsmemoryqt inst...
Page 92
Guid-19810098-1820-4765-8f0b-7d585ffc0c78 v7 table 100. Number of instances in the extension logic package logic block quantity with cycle time 3 ms 8 ms 100 ms slgapc 10 10 54 vsgapc 10 10 100 and 40 40 100 or 40 40 100 pulsetimer 20 20 49 gate — — 49 timerset 30 30 49 xor 10 10 69 lld — — 49 srmem...
Page 93
Guid-b258726e-1129-47c9-94f9-be634a2085fa v3 table 105. Elapsed time integrator with limit transgression and overflow supervision teigapc function cycle time (ms) range or value accuracy elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is greater 8 0 ~ 999999.9 s ±0.2% or ±100 ms ...
Page 94
Monitoring m12386-1 v15 table 109. Power system measurement cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u≤ 50 v ± 0.2% of u at u> 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i r ± 0.5% of i at 0.2 x i r i r ± 0.2% of i ...
Page 95
Guid-ed634b6d-9918-464f-b6a4-51b78129b819 v6 table 112. Voltage measurement phase-earth vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v guid-9b8a7fa5-9c98-4cbd-a162-7...
Page 96
M12760-1 v10 table 116. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 150 maximum number of analog inp...
Page 97
Guid-83b0f607-d898-403a-94fd-7fe8d45c73ff v7 table 118. Insulation supervision for liquid medium function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value ...
Page 98
Guid-f6b6ed6b-2488-483c-b068-3f4631f34dc8 v1 table 121. Transformer loss of life lolsptr function range or value accuracy service value, hot spot temperature – ±2.0% of expected value service value, top oil temperature – ±2.0% of expected value service value, loss of life – ±2.0% of expected value o...
Page 99
M12384-1 v7 table 126. Disturbance recorder function value buffer capacity maximum number of analog inputs 40 maximum number of binary inputs 352 maximum number of disturbance reports 100 maximum total recording time (3.4 s recording time and maximum number of channels, typical value) 340 seconds (1...
Page 100
Metering m13404-2 v5 table 129. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - semod153707-2 v5 table 130. Function for energy calculation and demand handling etpmmtr function range or val...
Page 101
Station communication m15031-1 v8 table 131. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–115200 bd protocol tc...
Page 102
M12589-1 v4 table 136. Slm – lon port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000 ft typically *) plastic fiber: 7 db (10m/35ft typically *) fiber diameter glass fiber: 62.5/125 mm plastic fiber:...
Page 103
Remote communication m12756-1 v10 table 140. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm graded-index multimode 50/125 µm singlemode 9/125 µm singlemode 9/125 µm peak emi...
Page 104
Hardware ied semod53385-1 v1 m11778-1 v6 table 141. Case material steel sheet front plate stainless steel with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) m12327-1 v4 table 142. Water and dust protection level according to iec 60529 front ip40 (ip54 with se...
Page 105
Connections, one blank slot is necessary between two adjacent io modules. Please refer to the ordering particulars for details. Guid-96676d5d-0835-44da-bc22-058fd18bdf34 v2 table 147. Num: communication ports num 4 ethernet ports 1 basic, 3 optional ethernet connection type sfp optical lc or galvani...
Page 106
Basic ied functions m11963-1 v5 table 149. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out m12331-1 v8 table 150. Time synchronization, time tagging function value time tagging accuracy of the synchrophasor da...
Page 107
Semod141136-2 v8 table 154. Irig-b quantity rated value number of channels irig-b 1 number of optical channels 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00...
Page 108
Inverse characteristic m12388-1 v21 table 155. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en-us i = i ...
Page 109
Table 156. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 3.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal i...
Page 110
Guid-19f8e187-4ed0-48c3-92f6-0d9eaa2b39bb v3 table 158. Ansi inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us re...
Page 111
Table 159. Iec inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 2.00 1.5 x i set ≤ i ≤ 20 x i ...
Page 112
Guid-2ae8c92e-5da8-487f-927d-8e553ee29240 v1 table 161. Ansi inverse time characteristics for voltage restrained time overcurrent protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristi...
Page 113
Semod116978-2 v10 table 163. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: ...
Page 114
Table 164. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en-us u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + ×...
Page 115
Table 165. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 3...
Page 116
24. Ordering for customized ied guid-43bac6e7-5454-464e-a4b0-97d2a602785d v7 table 166. General guidelines guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be us...
Page 117
Table 171. Differential functions function function identification ordering no position available qty selected qty notes and rules high impedance differential protection, single phase hzpdif 1mrk005904-hb 6 0-6 table 172. Impedance protection position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 ...
Page 118
Table 178. Frequency functions function function identification ordering no position available qty selected qty notes and rules underfrequency protection saptuf 1mrk005914-ac 1 0-6 overfrequency protection saptof 1mrk005914-bb 2 0-6 rate-of-change of frequency protection sapfrc 1mrk005914-cb 3 0-6 f...
Page 119
Table 186. Control functions function function identification ordering no position available qty selected qty notes and rules synchrocheck, energizing check and synchronizing sesrsyn 1mrk005917-ac 1 0-2 can only be ordered with apparatus control apc10/ apc15 synchrocheck, energizing check and synchr...
Page 120
Table 192. Monitoring functions function function identification ordering no position available qty selected qty notes and rules circuit breaker condition monitoring sscbr 1mrk005924-ha 1 00-18 fault locator lmbrflo 1mrk005925-xb 2 0-1 transformer insulation loss of life monitoring lolsptr 1mrk00592...
Page 121
Table 198. Power supply module selection power supply module ordering no selection notes and rules compression terminals 1mrk002960-ga c ringlug terminals 1mrk002960-ha r power supply module 24-60 vdc 1mrk002239-ab a power supply module 90-250 vdc 1mrk002239-bb b selected table 199. Human machine in...
Page 122
Table 200. Analog system selection analog system ordering no selection notes and rules when more than one trm is selected, the connector type on both trms must be the same (a compression or b ring lug). Slot position (front view/rear view) p40/x401 p41/x411 no transformer input module included x0 x0...
Page 123
Table 201. Maximum quantity of i/o modules, with compression terminals when ordering i/o modules, observe the maximum quantities according to the tables below. Note: standard order of location for i/o modules is bim-bom-som-iom-mim from left to right as seen from the rear side of the ied, but can al...
Page 124
Table 203. Binary input/output module selection binary input/ output modules ordering no selection notes and rules slot position (front view/rear view) p3/x31 p4/x41 p5/x51 p6/x61 p7/x71 p8/x81 p9/x91 p10/x101 p11/x111 p12/x121 p13/x131 p14/x141 p15/x151 p16/x161 1/2 case with 1 trm █ █ █ these blac...
Page 125
Table 203. Binary input/output module selection, continued binary input/ output modules ordering no selection notes and rules iom 8 inputs, 10+2 outputs, rl110, 110-125vdc, 50ma 1mrk000173-be n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 iom 8 inputs, 10+2 outputs, rl220, 220-250vdc, 50ma 1mrk000173-ce ...
Page 126
Table 204. Station communication, remote end serial communication and time synchronization selection station communication, remote end serial communication and time synchronization ordering no selection notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 ...
Page 127
25. Ordering for pre-configured ied guid-25af8847-411f-4f1d-91ed-0ed71c5aa8a1 v12 guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or...
Page 128
Software options ordering no #3 notes and rules no option x00 all fields in the ordering form do not need to be filled in. High impedance differential protection - 3 blocks 1mrk004001-ab a02 a02 only in a30/b30/d30, a07 only in c30 high impedance differential protection - 6 blocks 1mrk004001-ag a07 ...
Page 129
Mounting details with ip40 of protection from the front ordering no #6 notes and rules no mounting kit included x 19" rack mounting kit for 1/2 x 19" case or 2xrhgs6 or rhgs12 1mrk002420-bb a only for a30/b30/d30 19" rack mounting kit for 3/4 x 19" case or 3xrghs6 1mrk002420-ba b 19" rack mounting k...
Page 130
Binary input/output module and ma input module ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1 bim required in position p3 and 1 bom required in position p4. Products b30 and c30 require an extra bi...
Page 131
Binary input/output module and ma input module ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1 bim required in position p3 and 1 bom required in position p4. Products b30 and c30 require an extra bi...
Page 132
Station communication, remote end serial communication and time synchronization ordering no #11 notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 p30:5/x305 p30:6/x306 p30:6:1/x3061 p30:6:2/x3062 p31:1/x311 p31:2/x312 p31:3/x313 p32:2/x322 p32:3/x323 ld...
Page 133
26. Ordering for accessories accessories ip15151-1 v1 gps antenna and mounting details m12374-3 v5 gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, 20 m (appx. 65 ft) quantity: 1mrk 001 665-aa cable for antenna, 40 m (appx. 131 ft) quantity: 1mrk 001 665-ba interface...
Page 134
External resistor unit semod120228-4 v8 high impedance resistor unit with resistor and voltage dependent resistor 20-100v, 1ph quantity: 1 2 3 rk 795 101-ma high impedance resistor unit with resistor and voltage dependent resistor 20-100v, 3ph quantity: rk 795 101-mb high impedance resistor unit wit...
Page 135
User documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 511 401-uen ansi quantity: 1mrk 511 401-uus technical manual iec quantity: 1mrk 511 402-uen ansi quantity: 1mrk 511 402-uus commissioning manual iec quantity: 1mrk 511 403-uen ansi quantity...
Page 136
Ansi quantity: 1mrk 511 398-uus cyber security deployment guideline iec quantity: 1mrk 511 399-uen application guide, communication set-up iec quantity: 1mrk 505 382-uen reference information m2175-3 v4 for our reference and statistics we would be pleased to be provided with the following applicatio...
Page 137
137.
Page 138
— abb ab grid automation products 721 59 västerås, sweden phone: +46 (0) 21 32 50 00 abb.Com/protection-control © copyright 2017 abb. All rights reserved. Specifications subject to change without notice. 1mrk 511 404-ben.