ABB RED615 Product Manual

Manual is about: 615 series

Summary of RED615

  • Page 1

    Relion ® 615 series line differential protection and control red615 product guide.

  • Page 2

    Contents 1. Description.....................................................................3 2. Standard configurations.................................................3 3. Protection functions........................................................6 4. Application.....................................

  • Page 3

    1. Description red615 is a phase-segregated two-end line differential protection and control ied (intelligent electronic device) designed for utility and industrial power systems, including radial, looped and meshed distribution networks with or without distributed power generation. The red615s comm...

  • Page 4

    Table 2. Supported functions functionality a b c protection 1) three-phase non-directional overcurrent protection, low stage, instance 1 ● ● ● three-phase non-directional overcurrent protection, high stage, instance 1 ● ● ● three-phase non-directional overcurrent protection, high stage, instance 2 ●...

  • Page 5

    Table 2. Supported functions, continued functionality a b c master trip, instance 1 ● ● ● master trip, instance 2 ● ● ● control circuit-breaker control ● ● ● disconnector control, instance 1 ● 6) ● 6) ● 6) disconnector control, instance 2 ● 6) ● 6) ● 6) earthing switch control ● 6) ● 6) ● 6) disconn...

  • Page 6

    3. Protection functions the ied offers two-stage phase-segregated line differential protection, phase overcurrent protection, negative phase-sequence overcurrent protection and circuit-breaker failure protection. Depending on the standard configuration chosen, the basic functionality can be extended...

  • Page 7

    Guid-81a76312-4cc1-4ae8-a0a3-14c9800ee0e2 v3 en figure 2. Protection function overview of standard configuration b line differential protection and control 1mrs756500 f red615 product version: 4.0 abb 7.

  • Page 8

    Guid-4f4a066f-28c1-40fb-b3a6-b2cc3119e587 v3 en figure 3. Protection function overview of standard configuration c 4. Application red615 can be used in a variety of applications requiring an absolutely selective unit type protection system. The zone-of-protection of a line differential protection sy...

  • Page 9

    Combination of binary signal transfer and horizontal goose communication performance as to speed, selectivity and reliability are hard to match with conventional loss-of-mains protection. Red615 is the ideal ied for the protection of feeders in network configurations containing closed loops. Under n...

  • Page 10

    Guid-245166ba-1052-4edc-8c2d-9c968fa05c66 v3 en figure 5. Red615 protecting an interconnecting feeder between two primary distribution substations line differential protection and control 1mrs756500 f red615 product version: 4.0 10 abb.

  • Page 11

    Guid-9dc3bab9-9fa4-4a6d-83c4-e1a7fce811b0 v3 en figure 6. Line differential protection of an overhead line feeder using red615 with the standard configuration b line differential protection and control 1mrs756500 f red615 product version: 4.0 abb 11.

  • Page 12

    In figure 6 selectivity of earth-fault protection is ensured using binary signal transfer (bst) between the directional e/f protection stages of the local and remote end. The lowest directional e/ f stages are not used for tripping purposes, but set to detect earth-faults in the reverse direction. U...

  • Page 13

    Guid-9efbff56-5045-4b24-9c29-01c98aba81a1 v3 en figure 7. Line differential protection of an overhead line feeder using red615 with the standard configuration c and auto-reclosing option. Line differential protection and control 1mrs756500 f red615 product version: 4.0 abb 13.

  • Page 14

    In figure 7 uncoordinated auto-reclosing attempts are prevented by means of binary signal transfer (bst). During the auto-reclosing sequence a “wait” command is sent to the auto-reclosing function of the lower circuit breaker and thereby blocking the function. The upper circuit breaker is thereafter...

  • Page 15

    Guid-66eb52a0-21a1-4d1f-a1ef-61060b371384 v3 en figure 8. Utility power distribution network example using 615 series ieds, grid automation controller com600 and microscada pro guid-6984d893-45d5-427a-babf-f1e1015c18e2 v3 en figure 9. Industrial power system example using 615 series ieds, grid autom...

  • Page 16

    Further, the ied offers one control block which is intended for motor-operated control of one earthing switch control and its position indication. Two physical binary inputs and two physical binary outputs are needed in the ied for each controllable primary device taken into use. Depending on the ch...

  • Page 17

    8. Disturbance recorder the ied is provided with a disturbance recorder featuring up to 12 analog and 64 binary signal channels. The analog channels can be set to record either the waveform or the trend of the currents and voltage measured. The analog channels can be set to trigger the recording fun...

  • Page 18

    15. Protection communication and supervision the communication between the ieds is enabled by means of a dedicated fibre-optic communication channel. 1300 nm multi-mode or single-mode fibres with lc connectors are used for line differential communication. The channel is used for transferring the pha...

  • Page 19

    Red615 red615 fibre-optic line differential communication link protection communication and supervision binary signal transfer guid-8ce71cc9-f0ea-4be9-b693-173caea9fa58 v1 en figure 10. Fibre-optic protection communication link red615 red615 pilot wire line differential communication link protection...

  • Page 20

    All binary inputs and outputs contacts are freely configurable with the signal matrix or application configuration functionality of pcm600. Please refer to the input/output overview table and the terminal diagrams for more detailed information about the inputs and outputs. Table 5. Input/output over...

  • Page 21

    Modbus implementation supports rtu, ascii and tcp modes. Besides standard modbus functionality, the ied supports retrieval of time- stamped events, changing the active setting group and uploading of the latest fault records. If a modbus tcp connection is used, five clients can be connected to the ie...

  • Page 22

    Managed ethernet switch with rstp support managed ethernet switch with rstp support red615 ref615 ret615 reu615 rem615 client b client a network network guid-ab81c355-ef5d-4658-8ae0-01dc076e519c v3 en figure 12. Self-healing ethernet ring solution table 6. Supported station communication interfaces ...

  • Page 23

    19. Technical data table 7. Dimensions description value width frame 177 mm case 164 mm height frame 177 mm (4u) case 160 mm depth 201 mm (153 + 48 mm) weight complete ied 4.1 kg plug-in unit only 2.1 kg table 8. Power supply description type 1 type 2 u aux nominal 100, 110, 120, 220, 240 v ac, 50 a...

  • Page 24

    Table 9. Energizing inputs description value rated frequency 50/60 hz current inputs rated current, i n 1/5 a 1) thermal withstand capability: • continuously 4 a 20 a • for 1 s 100 a 500 a dynamic current withstand: • half-wave value 250 a 1250 a input impedance voltage inputs rated voltage 60...210...

  • Page 25

    Table 12. Signal outputs and irf output description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 15 a breaking capacity when the control-circuit time constant l/ r 1 a/0.25 a/0.15 a minimum contact load 10 ma at 5 v ac/dc table 13. D...

  • Page 26

    Table 16. Protection communication link connector fibre type wave length max. Distance permitted path attenuation 1) lc mm 62.5/125 or 50/125 μm 1300 nm 2 km lc sm 9/125 μm 2) 1300 nm 20 km 1) maximum allowed attenuation caused by connectors and cable altogether 2) use single-mode fibre with recomme...

  • Page 27

    Table 20. Environmental tests description type test value reference dry heat test • 96 h at +55ºc • 16 h at +70ºc 1) iec 60068-2-2 dry cold test • 96 h at -25ºc • 16 h at -40ºc iec 60068-2-1 damp heat test • 6 cycles (12 h + 12 h) at +25°c… +55°c, humidity >93% iec 60068-2-30 change of temperature t...

  • Page 28

    Table 21. Electromagnetic compatibility tests description type test value reference 1 mhz/100 khz burst disturbance test: iec 61000-4-18 iec 60255-22-1, class iii ieee c37.90.1-2002 • common mode 2.5 kv • differential mode 2.5 kv 3 mhz, 10 mhz and 30 mhz burst disturbance test: iec 61000-4-18 iec 60...

  • Page 29

    Table 21. Electromagnetic compatibility tests, continued description type test value reference voltage dips and short interruptions: 30%/10 ms 60%/100 ms 60%/1000 ms >95%/5000 ms iec 61000-4-11 power frequency immunity test: • common mode • differential mode binary inputs only 300 v rms 150 v rms ie...

  • Page 30

    Table 24. Product safety description reference lv directive 2006/95/ec standard en 60255-27 (2005) en 60255-1 (2009) table 25. Emc compliance description reference emc directive 2004/108/ec standard en 50263 (2000) en 60255-26 (2007) table 26. Rohs compliance description complies with rohs directive...

  • Page 31

    Protection functions table 27. Line differential protection (lnpldf) characteristics value operation accuracy 1) depending on the frequency of the current measured: f n ±2 hz low stage ±2.5% of the set value high stage ±2.5% of the set value minimum typical maximum high stage, operate time 2)3) 22 m...

  • Page 32

    Table 29. Binary signal transfer (bstggio) characteristic value signalling delay fiber optic link galvanic pilot wire link table 30. Three-phase non-directional overcurrent protection (phxptoc) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz phlp...

  • Page 33

    Table 31. Three-phase non-directional overcurrent protection (phxptoc) main settings parameter function value (range) step start value phlptoc 0.05...5.00 x i n 0.01 phhptoc 0.10...40.00 x i n 0.01 phiptoc 1.00...40.00 x i n 0.01 time multiplier phlptoc 0.05...15.00 0.01 phhptoc 0.05...15.00 0.01 op...

  • Page 34

    Table 32. Non-directional earth-fault protection (efxptoc) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz eflptoc ±1.5% of the set value or ±0.002 x i n efhptoc and efiptoc ±1.5% of set value or ±0.002 x i n (at currents in the range of 0.1…10 x...

  • Page 35

    Table 33. Non-directional earth-fault protection (efxptoc) main settings parameter function value (range) step start value eflptoc 0.010...5.000 x i n 0.005 efhptoc 0.10...40.00 x i n 0.01 efiptoc 1.00...40.00 x i n 0.01 time multiplier eflptoc 0.05...15.00 0.01 efhptoc 0.05...15.00 0.01 operate del...

  • Page 36

    Table 34. Directional earth-fault protection (defxpdef) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz deflpdef current: ±1.5% of the set value or ±0.002 x i n voltage ±1.5% of the set value or ±0.002 x u n phase angle: ±2° defhpdef current: ±1....

  • Page 37

    Table 35. Directional earth-fault protection (defxpdef) main settings parameter function value (range) step start value deflpdef 0.010...5.000 x i n 0.005 defhpdef 0.10...40.00 x i n 0.01 directional mode deflpdef and defhpdef 1=non-directional 2=forward 3=reverse time multiplier deflpdef 0.05...15....

  • Page 38

    Table 37. Transient/intermittent earth-fault protection (intrptef) main settings parameter function value (range) step directional mode intrptef 1=non-directional 2=forward 3=reverse - operate delay time intrptef 40...1200000 ms 10 voltage start value (voltage start value for transient ef) intrptef ...

  • Page 39

    Table 39. Admittance-based earth-fault protection (efpadm) main settings parameter values (range) unit step default description voltage start value 0.05...5.00 xun 0.01 0.05 voltage start value directional mode 1=non-directional 2=forward 3=reverse 2=forward directional mode operation mode 1=yo 2=go...

  • Page 40

    Table 40. Wattmetric based earth-fault protection (wpwde) characteristic value operation accuracy depending on the frequency of the current measured: fn ±2 hz current and voltage: ±1.5 % of the set value or ±0.002 x in power: ±3 % of the set value or ±0.002 x pn start time 1)2) typical 63 ms reset t...

  • Page 41

    Table 42. Harmonics earth-fault protection (haefptoc) characteristic value operation accuracy depending on the frequency of the current measured: fn ±2 hz ±5 % of the set value or ±0.004 x in start time 1)2) typical 77 ms reset time reset ratio typical 0.96 operate time accuracy in definite time mod...

  • Page 42

    Table 44. Residual overvoltage protection (rovptov) characteristic value operation accuracy depending on the frequency of the voltage measured: f n ±2 hz ±1.5% of the set value or ±0.002 x u n start time 1)2) minimum typical maximum u fault = 1.1 x set start value 55 ms 56 ms 58 ms reset time reset ...

  • Page 43

    Table 47. Negative phase-sequence overcurrent protection (nsptoc) main settings parameter function value (range) step start value nsptoc 0.01...5.00 x i n 0.01 time multiplier nsptoc 0.05...15.00 0.01 operate delay time nsptoc 40...200000 ms 10 operating curve type 1) nsptoc definite or inverse time...

  • Page 44

    Table 51. Circuit breaker failure protection (ccbrbrf) main settings parameter function value (range) step current value (operating phase current) ccbrbrf 0.05...1.00 x i n 0.05 current value res (operating residual current) ccbrbrf 0.05...1.00 x i n 0.05 cb failure mode (operating mode of function)...

  • Page 45

    Table 53. Three-phase thermal overload (t1pttr) main settings parameter function value (range) step env temperature set (ambient temperature used when the ambsens is set to off) t1pttr -50...100°c 1 current multiplier (current multiplier when function is used for parallel lines) t1pttr 1...5 1 curre...

  • Page 46

    Table 55. Three-phase inrush detection (inrphar) main settings parameter function value (range) step start value (ratio of the 2nd to the 1st harmonic leading to restraint) inrphar 5...100 % 1 operate delay time inrphar 20...60000 ms 1 table 56. Operation characteristics parameter values (range) ope...

  • Page 47

    Supervision functions table 57. Current circuit supervision (ccrdif) characteristic value operate time 1) 1) including the delay of the output contact. Table 58. Current circuit supervision (ccrdif) main settings parameter values (range) unit description start value 0.05...0.20 x i n minimum operate...

  • Page 48

    Control functions table 59. Autoreclosing (darrec) characteristic value operate time accuracy ±1.0% of the set value or ±20 ms line differential protection and control 1mrs756500 f red615 product version: 4.0 48 abb.

  • Page 49

    Measurement functions table 60. Three-phase current measurement (cmmxu) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz ±0.5% or ±0.002 x i n (at currents in the range of 0.01...4.00 x i n ) suppression of harmonics dft: -50 db at f = n x f n , w...

  • Page 50

    20. Local hmi the ied is available with two optional displays, a large one and a small one. The large display is suited for ied installations where the front panel user interface is frequently used and a single line diagram is required. The small display is suited for remotely controlled substations...

  • Page 51

    Table 65. Large display character size 1) rows in the view characters per row small, mono-spaced (6x12 pixels) 10 20 large, variable width (13x14 pixels) 8 8 or more 1) depending on the selected language 21. Mounting methods by means of appropriate mounting accessories the standard ied case for the ...

  • Page 52

    With a mechanical coding system preventing current measuring ied units from being inserted into a ied case for a voltage measuring ied unit and vice versa, i.E. The ied cases are assigned to a certain type of ied plug-in unit. 23. Selection and ordering data the ied type and serial number label iden...

  • Page 53

    # description 9 - 10 communication modules (serial/ethernet) serial rs-485 incl. Irig-b + line differential, multi mode fibre (lc) aa serial rs-485 incl. Irig-b + line differential, single mode fibre (lc) ab serial rs-485 incl. Irig-b + ethernet 100base-tx (rj-45) + line differential, multi mode fib...

  • Page 54

    # description 12 language english 1 english and german 3 english and swedish 4 english and spanish 5 english and russian 6 english and polish 7 english and portuguese (brazilian) 8 english and italian a english and french c english and czech e 13 front panel small lcd a large lcd with single line di...

  • Page 55

    24. Accessories and ordering data table 66. Pilot wire communication item order number pilot wire communication package including two pilot wire modems: rpw600am (master) and rpw600af (follower) rpw600amf diagnostics kit including the rpw-diagnostic tool, a diagnostic cable and a cd with necessary d...

  • Page 56

    Pcm600 basic/engineering and pcm600 engineering pro. Depending on the chosen variant, pcm600 offers extensive ied configuration functions such as ied signal configuration, application configuration, graphical display configuration including single line diagram configuration, and iec 61850 communicat...

  • Page 57

    Table 69. Supported functions function webhmi pcm600 basic/ engineering pcm600 engineering pro ied parameter setting ● ● ● saving of ied parameter settings in the ied ● ● ● signal monitoring ● ● ● disturbance recorder handling ● ● ● alarm led viewing ● ● ● access control management ● ● ● ied signal ...

  • Page 58

    26. Terminal diagrams guid-fbfa9940-e37d-4c32-a083-0367aaede267 v2 en figure 19. Terminal diagram for configuration a and c line differential protection and control 1mrs756500 f red615 product version: 4.0 58 abb.

  • Page 59

    Guid-a05d9233-4377-48d7-9f00-4218f0e7d4dc v2 en figure 20. Terminal diagram for configuration b line differential protection and control 1mrs756500 f red615 product version: 4.0 abb 59.

  • Page 60

    27. Certificates kema has issued an iec 61850 certificate level a1 for relion ® 615 series. Certificate number: 30920420-consulting 09-1712. Det norske veritas (dnv) has issued a type approval certificate for red615. Certificate number: e-11189. 28. References the www.Abb.Com/substationautomation po...

  • Page 61

    29. Functions, codes and symbols table 70. Red615 functions, codes and symbols function iec 61850 iec 60617 iec-ansi protection three-phase non-directional overcurrent protection, low stage phlptoc1 3i> (1) 51p-1 (1) three-phase non-directional overcurrent protection, high stage phhptoc1 3i>> (1) 51...

  • Page 62

    Table 70. Red615 functions, codes and symbols, continued function iec 61850 iec 60617 iec-ansi circuit breaker failure protection ccbrbrf1 3i>/io>bf 51bf/51nbf three-phase inrush detector inrphar1 3i2f> 68 master trip trpptrc1 master trip (1) 94/86 (1) trpptrc2 master trip (2) 94/86 (2) control circ...

  • Page 63

    30. Document revision history document revision/date product version history a/2008-10-03 1.1 first release b/2009-07-03 2.0 content updated to correspond to the product version c/2010-06-11 3.0 content updated to correspond to the product version d/2010-06-29 3.0 terminology updated e/2010-09-07 3....

  • Page 64

    64.

  • Page 68

    Contact us abb oy distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/substationautomation 1mrs756500 f © copyright 2012 abb. All rights reserved..