ABB RED615 Product Manual
Summary of RED615
Page 1
Line differential protection and control red615 product guide.
Page 2
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a contents disclaimer the information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may appear in thi...
Page 3
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a issued: october 008 revision: a / 0 october 008 1. Description red615, member of abb’s 615 product series, is a phase-segregated two-end line differential protection and control ied (intel- ligent electronic device...
Page 4
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a continued measurement transient disturbance recorder • three-phase current measurement • current sequence components • differential current measurement • bias current measurement • • = included 3. Protectionfunctio...
Page 5
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a 4. Application red615 can be used in a variety of applica- tions requiring an absolutely selective unit type protection system. The zone-of-protec- tion of a line differential protection system is the feeder sectio...
Page 6
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a fig. 3 red615 protecting an interconnecting feeder between two primary distribution substations under certain operational circumstances, such as maintenance of primary equipment or substation extension projects the...
Page 7
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a 5. Control the ied offers control of one circuit breaker with dedicated push-buttons for opening and closing. Interlocking schemes required by the application are configured with the signal matrix tool in pcm600. 6...
Page 8
Abb 8 line differential protection and control red615 product version: 1.1 1mrs756500 a the fault recording can be triggered by the start signal or the trip signal of a protection block, or by both. The available measurement modes include dft, rms and peak-to-peak. In addition, the maximum demand cu...
Page 9
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a cation, persists. The two high-set stages of the overcurrent protection are further by default released. 13.Accesscontrol to protect the ied from unauthorized access and to maintain information integrity, the ied i...
Page 10
Abb 10 line differential protection and control red615 product version: 1.1 1mrs756500 a supported communication interfaces and protocols 100base-tx rj-45 rs-485 +irig-b fibre-optic st iec 61850-8-1 • - - modbus rtu/ascii - • • modbus tcp - • - - • = supported bance files and storing of the latest f...
Page 11
Abb 11 line differential protection and control red615 product version: 1.1 1mrs756500 a power supply description value u aux nominal 100, 110, 120, 220, 240 v ac, 50 and 60 hz 48, 60, 110, 125, 220, 250 v dc u aux variation 38...110% of u n (38...264 v ac) 80...120% of u n (38.4...300 v dc) burden ...
Page 12
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a energizing inputs rated frequency 50/60 hz ± 5 hz current inputs rated current, i n 1/5 a 1) thermal withstand capability: • continuously • for 1 s for 1 s • for 10 s 20 a 500 a 100 a dynamic current withstand: •...
Page 13
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a irf relay change over - type signal output relay rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 15 a breaking capacity when the control-circuit time cons...
Page 14
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a degree of protection of flush-mounted ied front side ip 54 rear side, connection terminals ip 20 environmental conditions and tests environmental conditions operating temperature range -25...+55ºc (continuous) sh...
Page 15
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a radio frequency interference tests: • conducted, common mode • radiated, amplitude-modulated • radiated, pulse-modulated according to iec 61000-4-6 and iec 60255-22-6, level 3 10 v (emf), f = 150 khz...80 mhz acc...
Page 16
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a insulation and mechanical tests insulation tests dielectric tests: according to iec 60255-5 • test voltage 2 kv, 50 hz, 1 min 500 v, 50 hz, 1min, communication impulse voltage test: according to iec 60255-5 • tes...
Page 17
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a protection communication link, fibre-optic wavelength fibre type 2) connector permitted path attenuation 1) distance 1300 nm mm 62.5/125 μm lc ≤ 2 km 1300 nm sm 9/125 μm lc 2 - 20 km 1) maximum allowed attenuatio...
Page 18
Abb 18 line differential protection and control red615 product version: 1.1 1mrs756500 a binary signal transfer (bstggio) signalling delay 1) with the symmetrical communication channel (as when using dedicated fibre optic) 2) without additional delay in the communication channel (as when using dedic...
Page 19
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a 1) set operate delay time = 0,02 s, operate curve type = iec definite time, measurement mode = default (depends on stage), current before fault = 0.0 x in, fn = 50 hz, fault current in one phase with nominal freq...
Page 20
Abb 0 line differential protection and control red615 product version: 1.1 1mrs756500 a negative phase-sequence current protection (nsptoc) operation accuracy depending on the frequency of the current measured: f n = ±2hz ±1.5% of the set value or ±0.002 x i n start time 1) 2) minimum typical maximu...
Page 21
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a circuit breaker failure protection (ccbrbrf) main settings parameter function value (range) step current value (operating phase current) ccbrbrf 0.05...1.00 x i n 0.05 current value res (operating residual curren...
Page 22
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a operating characteristics parameter values (range) operating curve type 1=ansi ext. Inv. 2=ansi very. Inv. 3=ansi norm. Inv. 4=ansi mod inv. 5=ansi def. Time 6=l.T.E. Inv. 7=l.T.V. Inv. 8=l.T. Inv. 9=iec norm. Inv....
Page 23
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a 18.Displayoptions the ied is available with two optional dis- plays, a large one and a small one. Both lcd displays offer full front-panel user-interface functionality with menu navigation and menu views. The large...
Page 24
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a 19.Mountingmethods by means of appropriate mounting acces- sories the standard ied case for the 615 series ieds can be flush mounted, semi-flush mounted or wall mounted. The flush mount- ed and wall mounted ied cas...
Page 25
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a 21.Selectionand orderingdata the ied type and serial number label identi- fies the ied. The label is placed above the hmi on the upper part of the plug-in-unit. An order number label is placed on the side of the pl...
Page 26
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a h b d a a c a d a b b 1 a n n 1 x a # description 9 substation communication (serial) 1) 2) rs485 (connector incl. Irig-b) a st glass fi bre (rx/tx) b none n 10 protection and substation communication (ethernet) 1)...
Page 27
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a h b d a a c a d a b b 1 a n n 1 x a # description 12 language english 1 13 front panel small lcd a large lcd b 14 option 1 none n 15 option 2 none n 16 power supply 48...250 v dc, 100...240 v ac 1 17 vacant digit v...
Page 28
Abb 8 line differential protection and control red615 product version: 1.1 1mrs756500 a 22.Accessoriesand orderingdata mounting accessories item order nr semi-flush mounting kit 1mrs050696 wall mounting kit 1mrs050697 inclined semi-flush mounting kit 1mrs050831 19 ” rack mounting kit with cutout for...
Page 29
Abb line differential protection and control red615 product version: 1.1 1mrs756500 a tool function overview function webhmi pcm600 ied signal configuration (signal matrix tool) - • iec 61850 communication configuration, goose (communication configuration tool) - • modbus ® communication configurati...
Page 30
Abb 0 line differential protection and control red615 product version: 1.1 1mrs756500 a 24.Terminaldiagram fig. 10 terminal diagram of standard configuration a.
Page 31
Abb 1 line differential protection and control red615 product version: 1.1 1mrs756500 a 25.Functions,codes andsymbols red615 functions, codes and symbols functions iec 61850 iec 60617 ansi protection functions line differential protection, stabilized low stage and instantaneous high stage lnpldf 3∆i...
Page 32