ABB RED615 Product Manual

Manual is about: 615 series

Summary of RED615

  • Page 1

    Relion ® 615 series line differential protection and control red615 product guide.

  • Page 2

    Contents 1. Description..................................................................... 3 2. Standard configurations................................................. 3 3. Protection functions......................................................12 4. Application....................................

  • Page 3

    1. Description red615 is a phase-segregated two-end line differential protection and control relay designed for utility and industrial power systems, including radial, looped and meshed distribution networks with or without distributed power generation. Red615 is also designed for the protection of ...

  • Page 4

    Red615 at remote end sotf sotf communication protocols: iec 61850-8-1 modbus ® iec 60870-5-103 dnp3 interfaces: ethernet: tx (rj45), fx (lc) serial: serial glass fiber (st), rs-485, rs-232 redundant protocols: hsr prp rstp condition monitoring and supervision also available - binary signal transfer f...

  • Page 5

    Red615 at remote end sotf sotf communication protocols: iec 61850-8-1 modbus ® iec 60870-5-103 dnp3 interfaces: ethernet: tx (rj45), fx (lc) serial: serial glass fiber (st), rs-485, rs-232 redundant protocols: hsr prp rstp condition monitoring and supervision also available - binary signal transfer f...

  • Page 6

    Red615 at remote end also available - binary signal transfer function (bst) - disturbance and fault recorder - event log and recorded data - local/remote push button on lhmi - self-supervision - time synchronization: ieee 1588 v2, sntp, irig-b - user management - web hmi or and line differential pro...

  • Page 7

    Communication protocols: iec 61850-8-1/-9-2le modbus ® iec 60870-5-103 dnp3 interfaces: ethernet: tx (rj45), fx (lc) serial: serial glass fiber (st), rs-485, rs-232 redundant protocols: hsr prp rstp condition monitoring and supervision also available - binary signal transfer function (bst) - disturba...

  • Page 8

    Red615 at remote end communication protocols: iec 61850-8-1 iec 61850-9-2le modbus ® iec 60870-5-103 dnp3 interfaces: ethernet: tx (rj45), fx (lc) serial: serial glass fiber (st), rs-485, rs-232 redundant protocols: hsr prp rstp condition monitoring and supervision also available - binary signal tran...

  • Page 9

    Table 1. Standard configurations description std. Conf. Line differential protection a line differential protection with directional earth-fault protection and circuit-breaker condition monitoring b line differential protection with non-directional earth-fault protection and circuit-breaker conditio...

  • Page 10

    Table 2. Supported functions function iec 61850 a b c d e protection three-phase non-directional overcurrent protection, low stage phlptoc 1 1 1 three-phase non-directional overcurrent protection, high stage phhptoc 2 2 2 three-phase non-directional overcurrent protection, instantaneous stage phipto...

  • Page 11

    Table 2. Supported functions, continued function iec 61850 a b c d e fuse failure supervision seqspvc 1 1 protection communication supervision pcsitpc 1 1 1 1 1 runtime counter for machines and devices mdsopt 1 1 1 1 1 measurement disturbance recorder rdre 1 1 1 1 1 load profile record ldprlrc 1 1 1...

  • Page 12

    3. Protection functions the relay offers two-stage phase-segregated line differential protection, phase overcurrent protection, negative-sequence overcurrent protection and circuit breaker failure protection. Depending on the chosen standard configuration, the basic functionality can be extended by ...

  • Page 13

    3i red615 std. Conf. Ansi iec 46 50p/51p 51bf/51nbf 51p-1/51p-2 87l bst mcs 3i i2> 3i>>> 3i>/io>bf 3i>/3i>> 3Δi> bst mcs 3i a 3i r l clear esc i o u12 0. 0 kv p 0.00 kw q 0.00 kvar il2 0 a a red615 std. Conf. Ansi iec 46 50p/51p 51bf/51nbf 51p-1/51p-2 87l bst mcs 3i i2> 3i>>> 3i>/io>bf 3i>/3i>> 3Δi>...

  • Page 14

    3i red615 std. Conf. Ansi iec 46 47o-/59 47u+/27 50p/51p 51bf/51nbf 67n-1/67n-2 87l bst i2> u2>/3u> u13u 3i>>> 3i>/io>bf io> →/io>>→ 3Δi> bst e red615 std. Conf. Ansi iec 46 47o-/59 47u+/27 50p/51p 51bf/51nbf 67n-1/67n-2 87l bst i2> u2>/3u> u13u 3i>>> 3i>/io>bf io> →/io>>→ 3Δi> bst e io protection c...

  • Page 15

    Diagrams for switchgear bay solutions. The sld feature is especially useful when 615 series relays without the optional single-line diagram feature are used. The web hmi of com600 also provides an overview of the whole substation, including relay-specific single-line diagrams, which makes informatio...

  • Page 16

    Pcm600 ethernet switch utility: iec 60870-5-104 industry: opc com600 web hmi abb microscada pro/ system 800xa analog and binary horizontal goose communication iec 61850 pcm600 ethernet switch com600 web hmi analog and binary horizontal goose communication iec 61850 guid-4d002aa0-e35d-4d3f-a157-01f1a...

  • Page 17

    7. Measurements the relay continuously measures the phase currents, the symmetrical components of the currents and the residual current. If the relay includes voltage measurements, it also measures the residual voltage. The relay also calculates the demand value of the current over a user-selectable...

  • Page 18

    Information can also be accessed using the web browser- based user interface, either locally or remotely. 12. Recorded data the relay has the capacity to store the records of the 128 latest fault events. The records enable the user to analyze the power system events. Each record includes the phase, ...

  • Page 19

    And be assigned to the remote relay’s binary outputs or internal logics. The protection communication supervision continuously monitors the protection communication link. The relay immediately blocks the line differential protection function in case that severe interference in the communication link...

  • Page 20

    Addition, the binary input thresholds 16…176 v dc are selected by adjusting the relay’s parameter settings. All binary inputs and outputs contacts are freely configurable with the signal matrix or application configuration functionality of pcm600. Please refer to the input/output overview table and ...

  • Page 21

    For redundant ethernet communication, the relay offers two optical ethernet network interfaces. Ethernet network redundancy can be achieved using the high-availability seamless redundancy (hsr) protocol or the parallel redundancy protocol (prp) or a with self-healing ring using rstp in managed switc...

  • Page 22

    Ethernet switch redundancy box iec 61850 hsr redundancy box redundancy box ref615 ref620 ret620 rem620 ref615 scada devices not supporting hsr com600 guid-7996332d-7fc8-49f3-a4fe-fb4abb730405 v1 en figure 13. High availability seamless redundancy (hsr) solution the choice between the hsr and prp red...

  • Page 23

    Managed ethernet switch with rstp support managed ethernet switch with rstp support client b client a network a network b guid-ab81c355-ef5d-4658-8ae0-01dc076e519c v4 en figure 14. Self-healing ethernet ring solution all communication connectors, except for the front port connector, are placed on in...

  • Page 24

    The relay supports the following high accuracy time synchronization method with a time-stamping resolution of 4 µs required especially in process bus applications. • ptp (ieee 1588) v2 with power profile the ieee 1588 support is included in all variants having a redundant ethernet communication modu...

  • Page 25

    21. Technical data table 6. Dimensions description value width frame 177 mm case 164 mm height frame 177 mm (4u) case 160 mm depth 201 mm (153 + 48 mm) weight complete protection relay 4.1 kg plug-in unit only 2.1 kg table 7. Power supply description type 1 type 2 nominal auxiliary voltage u n 100, ...

  • Page 26

    Table 9. Energizing inputs (sensors) description value current sensor input rated current voltage (in secondary side) 75 mv...9000 mv 1) continuous voltage withstand 125 v input impedance at 50/60 hz 2...3 mΩ 2) voltage sensor input rated voltage 6 kv...30 kv 3) continuous voltage withstand 50 v inp...

  • Page 27

    Table 13. Double-pole power output relays with tcs function description value rated voltage 250 v ac/dc continuous contact carry 8 a make and carry for 3.0 s 15 a make and carry for 0.5 s 30 a breaking capacity when the control-circuit time constant l/r 48/110/220 v dc (two contacts connected in ser...

  • Page 28

    Table 17. Protection communication link connector fibre type wave length typical max. Length 1) permitted path attenuation 2) lc mm 62.5/125 or 50/125 μm 1300 nm 2 km lc sm 9/125 μm 3) 1300 nm 20 km 1) maximum length depends on the cable attenuation and quality, the amount of splices and connectors ...

  • Page 29

    Table 21. Electromagnetic compatibility tests description type test value reference 1 mhz/100 khz burst disturbance test iec 61000-4-18 iec 60255-26, class iii ieee c37.90.1-2002 • common mode 2.5 kv • differential mode 2.5 kv 3 mhz, 10 mhz and 30 mhz burst disturbance test iec 61000-4-18 iec 60255-...

  • Page 30

    Table 21. Electromagnetic compatibility tests, continued description type test value reference power frequency immunity test binary inputs only iec 61000-4-16 iec 60255-26, class a • common mode 300 v rms • differential mode 150 v rms conducted common mode disturbances 15 hz...150 khz test level 3 (...

  • Page 31

    Table 24. Environmental tests description type test value reference dry heat test • 96 h at +55ºc • 16 h at +70ºc 1) iec 60068-2-2 dry cold test • 96 h at -25ºc • 16 h at -40ºc iec 60068-2-1 damp heat test • 6 cycles (12 h + 12 h) at +25°c…+55°c, humidity >93% iec 60068-2-30 change of temperature te...

  • Page 32

    Protection functions table 28. Three-phase non-directional overcurrent protection (phxptoc) characteristic value operation accuracy depending on the frequency of the measured current: f n ±2 hz phlptoc ±1.5% of the set value or ±0.002 × i n phhptoc and phiptoc ±1.5% of set value or ±0.002 × i n (at ...

  • Page 33

    Table 29. Three-phase non-directional overcurrent protection (phxptoc) main settings parameter function value (range) step start value phlptoc 0.05...5.00 × i n 0.01 phhptoc 0.10...40.00 × i n 0.01 phiptoc 1.00...40.00 × i n 0.01 time multiplier phlptoc 0.05...15.00 0.01 phhptoc 0.05...15.00 0.01 op...

  • Page 34

    Table 31. Three-phase directional overcurrent protection (dphxpdoc) main settings parameter function value (range) step start value dphlpdoc 0.05...5.00 × in 0.01 dphhpdoc 0.10...40.00 × in 0.01 time multiplier dphxpdoc 0.05...15.00 0.01 operate delay time dphxpdoc 40...200000 ms 10 directional mode...

  • Page 35

    Table 33. Non-directional earth-fault protection (efxptoc) main settings parameter function value (range) step start value eflptoc 0.010...5.000 × i n 0.005 efhptoc 0.10...40.00 × i n 0.01 efiptoc 1.00...40.00 × i n 0.01 time multiplier eflptoc 0.05...15.00 0.01 efhptoc 0.05...15.00 0.01 operate del...

  • Page 36

    Table 34. Directional earth-fault protection (defxpdef) characteristic value operation accuracy depending on the frequency of the measured current: f n ±2 hz deflpdef current: ±1.5% of the set value or ±0.002 × i n voltage ±1.5% of the set value or ±0.002 × u n phase angle: ±2° defhpdef current: ±1....

  • Page 37

    Table 35. Directional earth-fault protection (defxpdef) main settings parameter function value (range) step start value deflpdef 0.010...5.000 × i n 0.005 defhpdef 0.10...40.00 × i n 0.01 directional mode deflpdef and defhpdef 1 = non-directional 2 = forward 3 = reverse time multiplier deflpdef 0.05...

  • Page 38

    Table 37. Admittance-based earth-fault protection (efpadm) main settings parameter function value (range) step voltage start value efpadm 0.01...2.00 × u n 0.01 directional mode efpadm 1 = non-directional 2 = forward 3 = reverse operation mode efpadm 1 = yo 2 = go 3 = bo 4 = yo, go 5 = yo, bo 6 = go...

  • Page 39

    Table 39. Wattmetric-based earth-fault protection (wpwde) main settings parameter function value (range) step directional mode wpwde 2 = forward 3 = reverse current start value wpwde 0.010...5.000 × i n 0.001 voltage start value wpwde 0.010...1.000 × u n 0.001 power start value wpwde 0.003...1.000 ×...

  • Page 40

    Table 42. Harmonics-based earth-fault protection (haefptoc) characteristic value operation accuracy depending on the frequency of the measured current: f n ±2 hz ±5% of the set value or ±0.004 × i n start time 1)2) typically 77 ms reset time typically 40 ms reset ratio typically 0.96 operate time ac...

  • Page 41

    Table 45. Negative-sequence overcurrent protection (nsptoc) main settings parameter function value (range) step start value nsptoc 0.01...5.00 × i n 0.01 time multiplier nsptoc 0.05...15.00 0.01 operate delay time nsptoc 40...200000 ms 10 operating curve type 1) nsptoc definite or inverse time curve...

  • Page 42

    Table 49. Residual overvoltage protection (rovptov) main settings parameter function value (range) step start value rovptov 0.010...1.000 × u n 0.001 operate delay time rovptov 40...300000 ms 1 table 50. Three-phase undervoltage protection (phptuv) characteristic value operation accuracy depending o...

  • Page 43

    Table 52. Three-phase overvoltage protection (phptov) characteristic value operation accuracy depending on the frequency of the measured voltage: f n ±2 hz ±1.5% of the set value or ±0.002 × u n start time 1)2) minimum typical maximum u fault = 1.1 × set start value 23 ms 27 ms 31 ms reset time typi...

  • Page 44

    Table 55. Positive-sequence undervoltage protection (psptuv) main settings parameter function value (range) step start value psptuv 0.010...1.200 × u n 0.001 operate delay time psptuv 40...120000 ms 10 voltage block value psptuv 0.01...1.0 × u n 0.01 table 56. Negative-sequence overvoltage protectio...

  • Page 45

    Table 59. Frequency protection (frpfrq) main settings parameter function value (range) step operation mode frpfrq 1 = freq 2 = freq> 3 = df/dt 4 = freq 5 = freq> + df/dt 6 = freq 7 = freq> or df/dt start value freq> frpfrq 0.9000...1.2000 × f n 0.0001 start value freq frpfrq 0.8000...1.1000 × f n 0....

  • Page 46

    Table 62. Three-phase thermal overload protection, two time constants (t2pttr) characteristic value operation accuracy depending on the frequency of the measured current: f n ±2 hz current measurement: ±1.5% of the set value or ±0.002 x i n (at currents in the range of 0.01...4.00 x i n ) operate ti...

  • Page 47

    Table 66. Circuit breaker failure protection (ccbrbrf) main settings parameter function value (range) step current value (operating phase current) ccbrbrf 0.05...1.00 × i n 0.05 current value res (operating residual current) ccbrbrf 0.05...1.00 × i n 0.05 cb failure mode (operating mode of function)...

  • Page 48

    Table 72. Multipurpose protection (mapgapc) main settings parameter function value (range) step start value mapgapc -10000.0...10000.0 0.1 operate delay time mapgapc 0...200000 ms 100 operation mode mapgapc over under - table 73. Fault locator (scefrflo) characteristic value measurement accuracy at ...

  • Page 49

    Table 75. Line differential protection with in-zone power transformer (lnpldf) characteristics value operation accuracy 1) depending on the frequency of the measured current: f n ±2 hz low stage ±2.5% of the set value high stage ±2.5% of the set value minimum typical maximum high stage, operate time...

  • Page 50

    Table 78. Operation characteristics parameter value (range) operating curve type 1 = ansi ext. Inv. 2 = ansi very. Inv. 3 = ansi norm. Inv. 4 = ansi mod inv. 5 = ansi def. Time 6 = l.T.E. Inv. 7 = l.T.V. Inv. 8 = l.T. Inv. 9 = iec norm. Inv. 10 = iec very inv. 11 = iec inv. 12 = iec ext. Inv. 13 = i...

  • Page 51

    Power quality functions table 79. Voltage variation (phqvvr) characteristic value operation accuracy ±1.5% of the set value or ±0.2% of reference voltage reset ratio typically 0.96 (swell), 1.04 (dip, interruption) table 80. Voltage unbalance (vsqvub) characteristic value operation accuracy ±1.5% of...

  • Page 52

    Control functions table 81. Autoreclosing (darrec) characteristic value operate time accuracy ±1.0% of the set value or ±20 ms table 82. Synchronism and energizing check (secrsyn) characteristic value operation accuracy depending on the frequency of the voltage measured: f n ±1 hz voltage: ±3.0% of ...

  • Page 53

    Condition monitoring and supervision functions table 84. Circuit-breaker condition monitoring (sscbr) characteristic value current measuring accuracy ±1.5% or ±0.002 x i n (at currents in the range of 0.1…10 x i n ) ±5.0% (at currents in the range of 10…40 x i n ) operate time accuracy ±1.0% of the ...

  • Page 54

    Measurement functions table 89. Three-phase current measurement (cmmxu) characteristic value operation accuracy depending on the frequency of the measured current: f n ±2 hz ±0.5% or ±0.002 × i n (at currents in the range of 0.01...4.00 × i n ) suppression of harmonics dft: -50 db at f = n × f n , w...

  • Page 55

    Table 94. Sequence voltage measurement (vsmsqi) characteristic value operation accuracy depending on the frequency of the voltage measured: f n ±2 hz at voltages in range 0.01…1.15 × u n ±1.0% or ±0.002 × u n suppression of harmonics dft: -50 db at f = n × f n , where n = 2, 3, 4, 5,… table 95. Thre...

  • Page 56

    Other functions table 97. Pulse timer function block (ptgapc) characteristic value operate time accuracy ±1.0% of the set value or ±20 ms table 98. Time delay off (8 pcs) (tofpagc) characteristic value operate time accuracy ±1.0% of the set value or ±20 ms table 99. Time delay on (8 pcs) (tongapc) c...

  • Page 57

    22. Local hmi the relay is available with two optional displays, a large one and a small one. The large display is suited for relay installations where the front panel user interface is frequently used and a single line diagram is required. The small display is suited for remotely controlled substat...

  • Page 58

    23. Mounting methods by means of appropriate mounting accessories the standard relay case for the 615 series relay can be flush mounted, semi- flush mounted or wall mounted. The flush mounted and wall mounted relay cases can also be mounted in a tilted position (25°) using special accessories. Furth...

  • Page 59

    26. Accessories and ordering data table 102. Pilot wire communication item order number pilot wire communication package including two pilot wire modems: rpw600am (master) and rpw600af (follower) rpw600amf diagnostics kit including the rpw-diagnostic tool, a diagnostic cable and a cd with necessary ...

  • Page 60

    Additional local hmi language to the protection relay. The update tool is activated using pcm600, and it enables multiple updates of the additional hmi language, thus offering flexible means for possible future language updates. Table 104. Tools configuration and setting tools version pcm600 2.6 (ro...

  • Page 61

    29. Terminal diagrams guid-fbfa9940-e37d-4c32-a083-0367aaede267 v2 en figure 20. Terminal diagram for configuration a and c line differential protection and control 1mrs756500 k red615 product version: 5.0 fp1 abb 61.

  • Page 62

    Guid-a05d9233-4377-48d7-9f00-4218f0e7d4dc v2 en figure 21. Terminal diagram for configuration b line differential protection and control 1mrs756500 k red615 product version: 5.0 fp1 62 abb.

  • Page 63

    Red615 16 17 19 18 x100 6 7 8 9 10 11 12 13 15 14 2 1 3 4 5 22 21 23 24 so2 tcs2 po4 so1 tcs1 po3 po2 po1 irf + - u aux 20 x110 3 4 5 6 7 8 9 10 bi 6 bi 5 bi 4 bi 3 bi 2 bi 8 bi 7 12 13 11 bi 1 1 2 x110 16 14 15 19 17 18 22 20 21 so3 so2 so1 23 so4 24 2) x120 1 2 3 4 5 6 7 8 9 10 11 12 14 io il1 il2...

  • Page 64

    Red615 16 17 19 18 x100 6 7 8 9 10 11 12 13 15 14 2 1 3 4 5 22 21 23 24 so2 tcs2 po4 so1 tcs1 po3 po2 po1 irf + - u aux 20 x110 3 4 5 6 7 8 9 10 bi 6 bi 5 bi 4 bi 3 bi 2 bi 8 bi 7 12 13 11 bi 1 1 2 x110 16 14 15 19 17 18 22 20 21 so3 so2 so1 23 so4 24 x1 lan x5 1 2 3 4 5 6 7 8 9 b/- a/+ / tx / rx gn...

  • Page 65

    30. Certificates dnv gl has issued an iec 61850 edition 2 certificate level a1 for relion ® 615 series. Certificate number: 7410570i-ope/inc 15-1136. Dnv gl has issued an iec 61850 edition 1 certificate level a1 for relion ® 615 series. Certificate number: 74105701-ope/inc 15-1145. Additional certif...

  • Page 66

    32. Functions, codes and symbols table 106. Functions included in the relay function iec 61850 iec 60617 iec-ansi protection three-phase non-directional overcurrent protection, low stage phlptoc1 3i> (1) 51p-1 (1) three-phase non-directional overcurrent protection, high stage phhptoc1 3i>> (1) 51p-2...

  • Page 67

    Table 106. Functions included in the relay, continued function iec 61850 iec 60617 iec-ansi three-phase overvoltage protection phptov1 3u> (1) 59 (1) phptov2 3u> (2) 59 (2) phptov3 3u> (3) 59 (3) positive-sequence undervoltage protection psptuv1 u1 47u+ (1) negative-sequence overvoltage protection n...

  • Page 68

    Table 106. Functions included in the relay, continued function iec 61850 iec 60617 iec-ansi high-impedance fault detection phiz1 hif (1) hiz (1) power quality current total demand distortion cmhai1 pqm3i (1) pqm3i (1) voltage total harmonic distortion vmhai1 pqm3u (1) pqm3v (1) voltage variation phq...

  • Page 69

    Table 106. Functions included in the relay, continued function iec 61850 iec 60617 iec-ansi rtd/ma measurement xrggio130 x130 (rtd) (1) x130 (rtd) (1) frequency measurement fmmxu1 f (1) f (1) iec 61850-9-2 le sampled value sending smvsender smvsender smvsender iec 61850-9-2 le sampled value receivin...

  • Page 70

    33. Document revision history document revision/date product version history a/2008-10-03 1.1 first release b/2009-07-03 2.0 content updated to correspond to the product version c/2010-06-11 3.0 content updated to correspond to the product version d/2010-06-29 3.0 terminology updated e/2010-09-07 3....

  • Page 71

    71.

  • Page 72

    Contact us abb oy medium voltage products, distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/mediumvoltage www.Abb.Com/substationautomation abb india limited, distribution automation maneja works vadodara-390013, india phone +91 265 672...