ABB RED615 Product Manual

Manual is about: 615 series

Summary of RED615

  • Page 1

    Relion ® 615 series line differential protection and control red615 product guide.

  • Page 2

    Contents 1. Description...........................................................3 2. Standard configurations.......................................3 3. Protection functions.............................................5 4. Application...........................................................7 5. S...

  • Page 3

    1. Description red615 is a phase-segregated two-end line differential protection and control ied (intelligent electronic device) designed for utility and industrial power systems, including looped and meshed distribution networks with or without decentralized power generation. Red615 is a member of ...

  • Page 4

    Table 2. Supported functions functionality a b c protection 1) line differential protection and related measurements, stabilized and instantaneous stages ● ● ● three-phase non-directional overcurrent, low stage, instance 1 ● ● ● three-phase non-directional overcurrent, high stage, instance 1 ● ● ● t...

  • Page 5

    Table 2. Supported functions, continued functionality a b c disconnector position indication, instance 1 ● ● ● disconnector position indication, instance 2 ● ● ● disconnector position indication, instance 3 ● ● ● earthing switch indication ● ● ● auto-reclosing - o o condition monitoring circuit-brea...

  • Page 6

    The operating time characteristic for the low stage can be set to definite time or inverse definite time mode. The direct inter-trip function ensures that both ends are always simultaneously tripped, independent of the fault current contribution. Guid-b8cbf357-474f-4f61-be28-d107515a09aa v2 en figur...

  • Page 7

    Guid-4f4a066f-28c1-40fb-b3a6-b2cc3119e587 v1 en figure 3. Protection function overview of standard configuration c 4. Application red615 can be used in a variety of applications requiring an absolutely selective unit type protection system. The zone-of- protection of a line differential protection s...

  • Page 8

    Guid-d4440c4d-6c02-4a37-a38b-1aedca9246fc v1 en figure 4. Closed loop network configuration with red615 line differential protection and control ieds under certain operational circumstances, such as maintenance of primary equipment or substation extension projects there will be a need for interconne...

  • Page 9

    Guid-9dc3bab9-9fa4-4a6d-83c4-e1a7fce811b0 v1 en line differential protection and control 1mrs756500 b red615 product version: 2.0 issued: 03.07.2009 abb 9.

  • Page 10

    Figure 6. Line differential protection of an overhead line feeder using red615 with the standard configuration b. Selectivity of earth-fault protection is ensured using binary signal transfer (bst) between the directional e/f protection stages of the local and remote end. The lowest directional e/f ...

  • Page 11

    Line differential protection and control 1mrs756500 b red615 product version: 2.0 issued: 03.07.2009 abb 11.

  • Page 12

    Guid-9efbff56-5045-4b24-9c29-01c98aba81a1 v1 en figure 7. Line differential protection of an overhead line feeder using red615 with the standard configuration c and auto-reclosing option. By means of binary signal transfer (bst) uncoordinated auto-reclosing attempts are prevented. During the auto- r...

  • Page 13

    Peer-to-peer goose communication iec 61850-8-1 iec 60870-5-104 com600 web hmi abb microscada ethernet switch pcm600 ref615 red615 ret615 ret615 ref615 red615 fibre optic ld communication binary signal transfer com600 peer-to-peer goose communication iec 61850-8-1 com600 web hmi pcm600 ethernet switc...

  • Page 14

    6. Control the ied offers control of one circuit breaker with dedicated push-buttons for opening and closing. Interlocking schemes required by the application are configured with the signal matrix in pcm600. 7. Measurement the ied continuously measures the phase currents, the symmetrical components ...

  • Page 15

    Signal of a protection block, or by both. The available measurement modes include dft, rms and peak-to-peak. In addition, the maximum demand current with time stamp is separately recorded. By default, the records are stored in a non-volatile memory. 11. Trip-circuit supervision the trip-circuit supe...

  • Page 16

    Two high-set stages of the overcurrent protection are further by default released. 15. Access control to protect the ied from unauthorized access and to maintain information integrity, the ied is provided with a four-level, role-based authentication system with administrator- programmable individual...

  • Page 17

    Setting and disturbance file records can be accessed using the iec 61850 protocol. Disturbance files are available to any ethernet- based application in the standard comtrade format. Further, the ied can send and receive binary signals from other ieds (so called horizontal communication) using the i...

  • Page 18

    Table 5. Supported station communication interfaces and protocols interfaces/protocols ethernet serial 100base-tx rj-45 rs-232/rs-485 fibre-optic st iec 61850 ● - - modbus rtu/ascii - ● ● modbus tcp/ip ● - - dnp3 (serial) - ● ● dnp3 tcp/ip ● - - iec 60870-5-103 - ● ● ● = supported line differential ...

  • Page 19

    18. Technical data table 6. Dimensions description value width frame 179.8 mm case 164 mm height frame 177 mm (4u) case 160 mm depth 194 mm (153 + 41 mm) weight ied 3.5 kg spare unit 1.8 kg table 7. Power supply description value u aux nominal 100, 110, 120, 220, 240 v ac, 50 and 60 hz 48, 60, 110, ...

  • Page 20

    Table 8. Energizing inputs description value rated frequency 50/60 hz ± 5 hz current inputs rated current, i n 1/5 a 1) thermal withstand capability: • continuously 4 a 20 a • for 1 s 100 a 500 a dynamic current withstand: • half-wave value 250 a 1250 a input impedance voltage inputs rated voltage 1...

  • Page 21

    Table 10. Signal outputs and irf output description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 15 a breaking capacity when the control-circuit time constant l/r 1 a/0.25 a/0.15 a minimum contact load 100 ma at 24 v ac/dc table 11. ...

  • Page 22

    Table 12. Single-pole power output relays description value rated voltage 250 v ac/dc continuous contact carry 8 a make and carry for 3.0 s 15 a make and carry for 0.5 s 30 a breaking capacity when the control-circuit time constant l/r dc, at 48/110/220 v dc 5 a/3 a/1 a minimum contact load 100 ma a...

  • Page 23

    Table 15. Environmental tests description type test value reference dry heat test (humidity • 16 h at +85ºc 1) iec 60068-2-2 dry cold test • 96 h at -25ºc • 16 h at -40ºc iec 60068-2-1 damp heat test, cyclic • 6 cycles (12 h + 12 h) at +25°c…+55°c, humidity >93% iec 60068-2-30 storage test • 96 h at...

  • Page 24

    Table 16. Electromagnetic compatibility tests description type test value reference 1 mhz burst disturbance test: iec 61000-4-18 and iec 60255-22-1, level 3 • common mode 2.5 kv • differential mode 1.0 kv electrostatic discharge test: iec 61000-4-2, iec 60255-22-2 and ieee c37.90.3.2001 • contact di...

  • Page 25

    Table 16. Electromagnetic compatibility tests, continued description type test value reference power frequency immunity test: • common mode • differential mode binary inputs only 300 v rms 150 v rms iec 61000-4-16 and iec 60255-22-7, class a voltage dips and short interruptions 30%/10 ms 60%/100 ms ...

  • Page 26

    Table 17. Insulation tests description type test value reference dielectric tests: iec 60255-5 • test voltage 2 kv, 50 hz, 1 min 500 v, 50 hz, 1min, communication impulse voltage test: iec 60255-5 • test voltage 5 kv, unipolar impulses, waveform 1.2/50 μs, source energy 0.5 j 1 kv, unipolar impulses...

  • Page 27

    Table 20. Product safety description reference lv directive 2006/95/ec standard en 60255-27 (2005) en 60255-6 (1994) table 21. Rohs compliance description complies with rohs directive 2002/95/ec table 22. Front port ethernet interfaces ethernet interface protocol cable data transfer rate front tcp/i...

  • Page 28

    Protection functions table 24. Line differential protection (lnpldf) characteristics value operation accuracy 1) depending on the frequency of the current measured: f n ±2 hz low stage ±2.5% of the set value high stage ±2.5% of the set value minimum typical maximum high stage, operate time 2)3) 22 m...

  • Page 29

    Table 25. Line differential protection (lnpldf) main settings parameter values (range) unit description high operate value 200...4000 % i n instantaneous stage operate value low operate value 10...200 % i n basic setting for the stabilized stage start operate delay time 45...200000 ms operate delay ...

  • Page 30

    Table 27. Three-phase non-directional overcurrent protection (phxptoc) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2hz phlptoc ±1.5% of the set value or ±0.002 x i n phhptoc and phiptoc ±1.5% of set value or ±0.002 x i n (at currents in the range ...

  • Page 31

    Table 28. Three-phase non-directional overcurrent protection (phxptoc) main settings parameter function value (range) step start value phlptoc 0.05...5.00 x i n 0.01 phhptoc 0.10...40.00 x i n 0.01 phiptoc 1.00...40.00 x i n 0.01 time multiplier phlptoc 0.05...15.00 0.05 phhptoc 0.05...15.00 0.05 op...

  • Page 32

    Table 29. Non-directional ef protection (efxptoc) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2hz eflptoc ±1.5% of the set value or ±0.002 x i n efhptoc and efiptoc ±1.5% of set value or ±0.002 x i n (at currents in the range of 0.1…10 x i n ) ±5....

  • Page 33

    Table 30. Non-directional ef protection (efxptoc) main settings parameter function value (range) step start value eflptoc 0.010...5.000 x i n 0.005 efhptoc 0.10...40.00 x i n 0.01 efiptoc 1.00...40.00 x i n 0.01 time multiplier eflptoc 0.05...15.00 0.05 efhptoc 0.05...15.00 0.05 operate delay time e...

  • Page 34

    Table 31. Directional ef protection (defxpdef) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2hz deflpdef current: ±1.5% of the set value or ±0.002 x i n voltage ±1.5% of the set value or ±0.002 x u n phase angle: ±2° defhpdef current: ±1.5% of the ...

  • Page 35

    Table 32. Directional ef protection (defxpdef) main settings parameter function value (range) step start value deflpdef 0.01...5.00 x i n 0.005 defhpdef 0.10...40.00 x i n 0.01 directional mode deflpdef and defhpdef 1=non-directional 2=forward 3=reverse time multiplier deflpdef 0.05...15.00 0.05 def...

  • Page 36

    Table 34. Transient/intermittent earth-fault protection (intrptef) main settings parameter function value (range) step directional mode intrptef 1=non-directional 2=forward 3=reverse operate delay time intrptef 40...1200000 ms 10 voltage start value (voltage start value for transient ef) intrptef 0....

  • Page 37

    Table 36. Negative phase-sequence overcurrent protection (nsptoc) main settings parameter function value (range) step start value nsptoc 0.01...5.00 x i n 0.01 time multiplier nsptoc 0.05...15.00 0.05 operate delay time nsptoc 40...200000 ms 10 operating curve type 1) nsptoc definite or inverse time...

  • Page 38

    Table 39. Circuit breaker failure protection (ccbrbrf) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2hz ±1.5% of the set value or ±0.002 x i n operate time accuracy ±1.0% of the set value or ±20 ms table 40. Circuit breaker failure protection (ccbr...

  • Page 39

    Table 42. Three-phase thermal overload (t1pttr) main settings parameter function value (range) step env temperature set (ambient temperature used when the ambsens is set to off) t1pttr -50...100°c 1 current multiplier (current multiplier when function is used for parallel lines) t1pttr 1...5 1 curre...

  • Page 40

    Table 43. Three-phase inrush current detection (inrphar) characteristic value operation accuracy at the frequency f=f n current measurement: ±1.5% of the set value or ±0.002 x i n ratio i2f/i1f measurement: ±5.0% of the set value reset time +35 ms / -0 ms reset ratio typical 0.96 operate time accura...

  • Page 41

    Table 45. Operation characteristics parameter values (range) operating curve type 1=ansi ext. Inv. 2=ansi very. Inv. 3=ansi norm. Inv. 4=ansi mod inv. 5=ansi def. Time 6=l.T.E. Inv. 7=l.T.V. Inv. 8=l.T. Inv. 9=iec norm. Inv. 10=iec very inv. 11=iec inv. 12=iec ext. Inv. 13=iec s.T. Inv. 14=iec l.T. ...

  • Page 42

    Table 47. Current circuit supervision (ccrdif) main settings parameter values (range) unit description start value 0.05...0.20 x i n minimum operate current differential level maximum operate current 1.00...5.00 x i n block of the function at high phase current control functions table 48. Autoreclos...

  • Page 43

    Table 51. Residual current measurement (rescmmxu) characteristic value operation accuracy depending on the frequency of the current measured: f/f n = ±2hz ±0.5% or ±0.002 x i n at currents in the range of 0.01...4.00 x i n suppression of harmonics dft: -50db at f = n x f n , where n = 2, 3, 4, 5, … ...

  • Page 44

    19. Display options the ied is available with two optional displays, a large one and a small one. Both lcd displays offer full front-panel user- interface functionality with menu navigation and menu views. The large display offers increased front-panel usability with less menu scrolling and improved...

  • Page 45

    20. Mounting methods by means of appropriate mounting accessories the standard ied case for the 615 series ied can be flush mounted, semi-flush mounted or wall mounted. The flush mounted and wall mounted ied cases can also be mounted in a tilted position (25°) using special accessories. Further, the...

  • Page 46

    22. Selection and ordering data the ied type and serial number label identifies the protection ied. The label is placed above the hmi on the upper part of the plug-in-unit. An order number label is placed on the side of the plug-in unit as well as inside the case. The order number consists of a stri...

  • Page 47

    The communication module harware determines the available communication protocols. Choose the digits from one of the blue communication rows below to define the corect digits for digits 9-11. Note that the communication options are not dependant on the chosen standard configuration. H b d c a c a d ...

  • Page 48

    Guid-e479979d-a01f-4109-8fc4-67601f1346a6 v3 en h b d c a c a d a b b 1 a a n 1 x c # description 12 language english 1 english and german 3 english and spanish 5 english and russian 6 english and portugese (brasilian) 8 13 front panel small lcd a large lcd b 14 option 1 auto-reclosing 1) a none n 1...

  • Page 49

    23. Accessories and ordering data table 55. Cables item order number cable for optical sensors for arc protection 1.5 m 1mrs120534-1.5 cable for optical sensors for arc protection 3.0 m 1mrs120534-3.0 cable for optical sensors for arc protection 5.0 m 1mrs120534-5.0 table 56. Mounting accessories it...

  • Page 50

    Connect and interact with the ied. The connectivity packages reduce the risk of errors in system integration, minimizing device configuration and set-up times. Table 57. Tools configuration and setting tools version pcm600 2.0 sp2 or later web-browser based user interface ie 7.0 or later red615 conn...

  • Page 51

    25. Terminal diagrams guid-fbfa9940-e37d-4c32-a083-0367aaede267 v2 en figure 16. Terminal diagram for configuration a and c line differential protection and control 1mrs756500 b red615 product version: 2.0 issued: 03.07.2009 abb 51.

  • Page 52

    Guid-a05d9233-4377-48d7-9f00-4218f0e7d4dc v1 en figure 17. Terminal diagram for configuration b line differential protection and control 1mrs756500 b red615 product version: 2.0 issued: 03.07.2009 52 abb.

  • Page 53

    26. References the www.Abb.Com/substationautomation portal offers you information about the distribution automation product and service range. You will find the latest relevant information on the red615 protection ied on the product page . The download area on the right hand side of the web page con...

  • Page 54

    27. Functions, codes and symbols table 59. Red615 functions, codes and symbols functionality iec 61850 iec 60617 iec-ansi protection three-phase non-directional overcurrent protection, low stage, instance 1 phlptoc1 3i> (1) 51p-1 (1) three-phase non-directional overcurrent protection, high stage, in...

  • Page 55

    Table 59. Red615 functions, codes and symbols, continued functionality iec 61850 iec 60617 iec-ansi negative-sequence overcurrent protection, instance 2 nsptoc2 i 2 > (2) 46 (2) phase discontinuity protection pdnsptoc1 i 2 /i 1 > 46pd three-phase thermal protection for feeders, cables and distributi...

  • Page 56

    Table 59. Red615 functions, codes and symbols, continued functionality iec 61850 iec 60617 iec-ansi three-phase current measurement, instance 1 cmmxu1 3i 3i sequence current measurement csmsqi1 i 1 , i 2 , i 0 i 1 , i 2 , i 0 residual current measurement, instance 1 rescmmxu1 i 0 i n residual voltag...

  • Page 57

    57.

  • Page 60

    Contact us abb oy distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/substationautomation 1mrs756500 b © copyright 2009 abb. All rights reserved..