ABB REQ650 Product Manual - page 15
Selector mini switch VSGAPC
SEMOD158756-5 v8
The Selector mini switch VSGAPC function block is a
multipurpose function used for a variety of applications, as a
general purpose switch.
VSGAPC can be controlled from the menu, from a symbol on
the single line diagram (SLD) on the local HMI or from Binary
inputs
Generic communication function for Double Point indication
DPGAPC
SEMOD55850-5 v6
Generic communication function for Double Point indication
DPGAPC function block is used to send double indications to
other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It
is especially used in the interlocking station-wide logics.
Single point generic control 8 signals SPC8GAPC
SEMOD176462-4 v9
In this way, simple commands can be sent directly to the IED
outputs, without confirmation. The commands can be pulsed
or steady with a settable pulse time.
SEMOD158591-5 v7
Single command, 16 signals
M12446-6 v5
The IEDs can receive commands either from a substation
automation system or from the local HMI. The command
function block has outputs that can be used, for example, to
control high voltage apparatuses or for other user defined
functionality.
8. Logic
M12275-3 v10
A function block for protection tripping is always provided as
basic for each circuit breaker involved in the tripping of the
fault. It provides a settable pulse prolongation to ensure a trip
pulse of sufficient length, as well as all functionality necessary
for correct co-operation with autoreclosing functions.
The trip function block also includes a settable latch
functionality for breaker lock-out.
Trip matrix logic TMAGAPC
M15321-3 v11
The trip matrix logic function has 3 output signals and these
outputs can be connected to physical tripping outputs
according to the specific application needs for settable pulse
or steady output.
Group alarm logic function ALMCALH
GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v3
The group alarm logic function ALMCALH is used to route
several alarm signals to a common indication, LED and/or
contact, in the IED.
Group warning logic function WRNCALH
GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v3
The group warning logic function WRNCALH is used to route
several warning signals to a common indication, LED and/or
contact, in the IED.
Group indication logic function INDCALH
GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v3
The group indication logic function INDCALH is used to route
several indication signals to a common indication, LED and/or
contact, in the IED.
Basic configurable logic blocks
M11396-4 v15
The basic configurable logic blocks do not propagate the time
stamp and quality of signals (have no suffix QT at the end of
their function name). A number of logic blocks and timers are
always available as basic for the user to adapt the
configuration to the specific application needs. The list below
shows a summary of the function blocks and their features.
These logic blocks are also available as part of an extension
logic package with the same number of instances.
• AND function block. Each block has four inputs and two
outputs where one is inverted.
• GATE function block is used for whether or not a signal
should be able to pass from the input to the output.
• INVERTER function block that inverts one input signal to
the output.
• LLD function block. Loop delay used to delay the output
signal one execution cycle.
• OR function block. Each block has up to six inputs and two
outputs where one is inverted.
• PULSETIMER function block can be used, for example, for
pulse extensions or limiting of operation of outputs, settable
pulse time.
• RSMEMORY function block is a flip-flop that can reset or
set an output from two inputs respectively. Each block has
two outputs where one is inverted. The memory setting
controls if, after a power interruption, the flip-flop resets or
returns to the state it had before the power interruption.
RESET input has priority.
• SRMEMORY function block is a flip-flop that can set or
reset an output from two inputs respectively. Each block
has two outputs where one is inverted. The memory setting
controls if, after a power interruption, the flip-flop resets or
returns to the state it had before the power interruption.
The SET input has priority.
• TIMERSET function has pick-up and drop-out delayed
outputs related to the input signal. The timer has a settable
time delay.
• XOR function block. Each block has two outputs where one
is inverted.
Fixed signal function block
M15322-3 v11
The Fixed signals function FXDSIGN generates nine pre-set
(fixed) signals that can be used in the configuration of an IED,
either for forcing the unused inputs in other function blocks to
1MRK 505 358-BEN B
Breaker protection REQ650 2.1 IEC
Product version: 2.1
ABB
15