AirPac COOLIT3000 Instruction Manual - page 8
Control Panel
Supply Air Vent
Condenser
Air Discharge
UNIT OVERVIEW—COOLIT 3000
FRONT VIEW
Keyed Access Door to Condensate Tanks,
Internal Condensate Pump System and Stor-
age for Vinyl Tubing
5
Keyed Filter
Access
14
If it is necessary to operate the COOLIT3000 continually
without threat of automatic shut-off and loss of cooling when
tanks are full, you will need to utilize the integral condensate
pump option. Selecting the automatic condensate pump
method is a snap.
1.
Open the front door of the COOLIT3000.
2.
Locate the red vinyl
tube attached to the
condensate pump.
3.
Disconnect the red
vinyl tube at the
barbed connector to
the condensate
pump. Connect the
vinyl tube (8’ pro-
vided) to barbed fitting of the condensate pump.
Direct the other end of the tubing through the unit to
your drain connection.
4.
Depending on the length of your drain line, you may
need to add more tubing or soft copper tubing de-
pending on the building codes in your area. Tubing is
3/8” ID. The condensate pump in your COOLIT3000
has a 15’ lift capability. If lift is exceeded, the pump
will shut down.
REMOVING THE CONDENSATE
continued
Automatic
Condensate
Draining
The condensate drain line installation must
comply with your local building codes .
Consult local building codes before installing
the condensate line.
CAUTION:
Condensate pump and drain installation and
maintenance instructions specific to your
equipment are included with this manual .
NOTE: