Bacharach Microprocessor Module Replacement Kit Instruction Manual - page 11
Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors
3015-5547 Rev 4
11
d. Use the UP and DOWN arrow keys to select the NUM ZONES INSTALLED setting and press ENTER.
e. Use the UP and DOWN arrow keys to choose the number of physical zones (solenoids) installed in your
Multi-Zone (i.e., 4, 8, 12, or 16 zones). Press ENTER to save the changes, or ESC to abort the changes.
NOTE
The NUM ZONES INSTALLED setting defines the maximum number of zones that your
Multi-Zone is capable of measuring (i.e., a hardware parameter), NOT the number of zones
defined by your application. For example, your Multi-Zone may be equipped with 16 hardware
solenoids (zones), but your application uses only 13 of those zones. In this case, NUM ZONES
INSTALLED is set to 16. You must set the tubing length to 0 ft for the other 3 unused zones.
f.
Using steps (c) through (e) as guides, change the other system settings as required. The other system
settings are:
•
ALM ACK MODE
•
REZERO MODE
•
AUDIBLEALARM
•
RS485 BAUD
•
ZONE HOLD
•
NODE ADDRESS
•
DETECTION LIMIT
•
PASSWORD.
•
LOOP2 FACTOR
g. When all changes are complete, press ESC to return to the Main Setup Screen.
Figure 17. Main Setup Screen
h. Use the DOWN arrow key to select the ZONES setting and press ENTER. There is a Setup Menu for each
zone specified by the NUM ZONES INSTALLED setting set previously.
Figure 18. Zone #1 Setup Screens