Bacharach Microprocessor Module Replacement Kit Instruction Manual - page 12
Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors
12
3015-5547 Rev 4
i.
Use the LEFT and RIGHT arrow keys to scroll through all Zone Setup Screens.
j.
Select and change the zone settings as required or as recorded earlier in the table on page 2. The zone
settings are:
•
LOCATION
•
LOG INTERVAL
•
REFRIGERANT
•
LEAK LEVEL
•
DISTANCE (length of tubing)
•
SPILL LEVEL
•
TEMP AT ZONE
•
EVAC LEVEL.
k. When all changes are complete, press ESC to return to the Main Setup Screen.
l.
Press ESC to return to the Main Run Screen.
m. After configuring all parameters, press the CPU reset button on the bottom edge at the center of the main
circuit board (refer to Figure 19). The monitor will restart and enter the warm-up state.
Figure 19. Location of CPU Reset Button
n. Confirm that there are no faults indicated, and reconnect the 12-position screw terminal.
o. Close the front panel and reinstall the panel screws.
∇
∇
∇