Eaton Powerware 9395 Specification Sheet - page 4
UPS Rating (0.9 power factor)
kVA
225 275 550
kW
202 250 500
General Characteristics
Efficiency
Upto95%
ParallelCapability
Upto3modules,550kVAmaximum
AudibleNoise
<65dBA@1meter
Altitude(max)
2000mat40ºC(104ºF)
N+1RedundancyCapable Yes
FieldUpgradeable
Yes,275kVAincrements
SystemBypassModule
Included
Input Characteristics
Voltage
480Vstandard;208Vand600Vwithisolation
transformeroption
VoltageRange
+10%/-15%
FrequencyRange
55-65Hz
PowerFactor
0.99(minimum)
InputCurrentDistortion
<3%(noinputfilterrequired)
SoftStartCapability
Yes
InternalBackfeed
Yes
Protection
Output Characteristics
Voltage
480Vstandard;208Vand600Vwithisolation
transformeroption
Regulation
±1%
Inverter
PWMwithIGBTswitching
VoltageTHD
<2%(100%linearload);<5%(non-linearload)
LoadPowerFactorRange Uptoa.9powerfactorleadingwithoutde-rating
Battery
BatteryTypes
VRLA,AGM,Gel,Wet
BatteryVoltage
480V
TemperatureCompensation Optional
ChargingMethod
AdvancedBatteryManagementtechnology
Dimensions & Weights
225kVA,275kVA
52.4”wx34.3”dx73.7”h
1786lb.
225kVAredundant,
73.7”wx34.3”dx73.7”h
2875lb.
275kVAredundant
550kVA
73.7”wx34.3”dx73.7”h
2977lb.
550kVAredundant
95.0”wx34.3”dx73.7”h
4153lb.
Fieldupgrademodule,
21.3”wx34.3”dx73.7”h
1176lb
225or275kVA
User Benefits
ControlPanel(LCD)
8linesx40characters
BatteryStartup
Standard
FrequencyConversion
Standard
RemoteDisplayPanel
Optional
Multi-language
Standard
BuildingAlarmInputs
6(galvanicisolated)
Serviceability
Back/SideAgainstWall
Standard
Installation
Options
ExternalMaintenanceBypass
PowerwarePDU,RPP,andSTS
IsolationTransformer
OutputTransformer
MaintenanceBypassModule
Certifications
Safety
UL1778,cUL
EMC
FCCClass,A
Surge
ANSIC62,41Cat,A&B
eNotify Remote Monitoring
24x7remotemonitoringof43UPSandbatteryalarms,dailyheartbeatcheck
andmonthlyreportConnectUPSWeb/SNMP/xHubcard
Communications
SoftwareCompatibility-PowerVision
®
,LanSafe
®
,
FORESEER
®
,PowerXpert
CommunicationCards-StandardsystemincludesoneConnectUPSWeb/SNMPcard
withanEnvironmentalMonitoringProbe.Fourcommunicationbaysstandard.
Thefollowingconnectivityoptionscanbeinstalledatanytime:
-ConnectUPSWeb/SNMP/xHub
-ModusCard
-RelayInterfaceCard(UseforAS400s)
-IndustrialRelayCard(5A@120V)
-HotSyncCANBridgeCardprovidesCANcommunications,isolatedRS-485port
-EnvironmentalMonitoringProbe(EMP)
3
RemoteInputs/Outputs-Sixbuildingalarmsinputsandonesummaryalarmcontact
(5A@120V)standard
RemotePanel-Eightbacklitstatusindicatorlampsplusanaudiblehorn
3
TechnicalSpecifications
2
©2007EatonCorporation
AllRightsReserved
PrintedinUSA
9395FXA
March2007
EUROPE/MIDDLEEAST/AFRICA
Denmark:45.3686.7910
Finland:358.94.52.661
France:33.1.6012.7400
Germany:49.7841.666.0
Italy:39.02.66.04.05.40
Norway:47.23.03.65.50
Sweden:46.8.598.940.00
UnitedKingdom:44.1753.608.700
ASIAPACIFIC
Australia/NZ:61.2.9693.9366
China:86.21.6361.5599
HK/Korea/Taiwan:852.2745.6682
India:91.11.2649.9414to18
Singapore/SEA:65.6825.1668
Powerware,PowerVision,FORESEER,Power
Xpert,LanSafe,andABMaretrademarksof
EatonElectricalInc.
2. Due to continuing improvements, specifications are
subject to change without notice.
3.RequirestheConnectUPSWeb/SNMP/xHubcard.
Powerware® 9395-825 - Available Fall 2008
Uninterruptible Power System (UPS)
225 to 825 KVA