2 - INSTALLATION
2.1 Before installing
In order to start the humidifier / cooler UCP, the following conditions are required:
• connection to the electric power supply with voltage and frequency suitable for
the machine and with grounding and safety devices;
• connection to water supply (pressure required: between 2 and 6 atm);
• a dynamic ventilation system (air flow >1 m/s)
• where expected: water drain connection.
The installation must meet the safety requirements
provided by local regulation in force.
Make sure that all the connections necessary to operate the equipment have been properly prepared.
2.2 Positioning
The UCP humidifier must be installed either in front of a stirring air fan or as a part of a dynamic
ventilation system
The humidifier / cooler UCP must be installed horizontally, hanging off the ground, with the non-
atomized water tank siding down.
Use the proper holes at the base of the motor for hanging the machine holding it in the correct
operating position with an appropriate fixing system avoiding vibration (the distance between
holes is shown in Figure 2.1; use vibrations reducer devices);
Fig. 2.1 Posizione fori per fissaggio
The machine must be installed maintaining a slight upward inclination.
The positioning of the UCP must be done by maintaining the minimum recommended distance that allows the
correct operation of the machine and to perform maintenance when needed.
Choose, depending on the type on installation adopted, the most suitable position for the humidification and the
cooling of the environment.
These humidifiers could be installed in air treatment units or inside canalizations for air distribution.
Is necessary to predispose a drain system for non-atomized water.
It’s almost necessary, in order to maximize the fog quality, to adopt a drop separator (see fig. 2.2).
When the humidifier is used in combination with a fan; in order to prevent fog condensation on walls, maintain a
minimum distance of 1m from the ceiling and the walls, while, for what concerns the front wall, the distance will
have to be calculated based on the fan model chosen and the amount of water atomized.