FRANCO UCP Instruction Manual For Use And Maintenance - page 15
FRANCO srl Manual of use and maintenance UCP
15
The installment of the machine must meet the safety distance and protections in
accordance with the norm DIN EN 294 – 4, 4.1, 4.2. The machine must
be placed at least at 2.5 meters above the ground level (if used without protections.
Fig. 2.2 - A.T.U. section with UCP
Fig. 2.3 – fan installation example
2.3 Electrical connection
The installation involves the use of a humidistat or a thermostat ON/OFF controlling the power
of the machine; it is still possible to use, alternatively, a switch ON/OFF, in this case the start
and stop of the machine must be done manually.
The choice, however, does not affect the installation procedure described below.
•
Electrical connections must be undertaken by specialized, experienced and trained
technicians, in accordance with the current legislation.
•
Ensure that the electricity supply specifications correspond to those indicated in the
in this manual.
•
It is obligatory that the device is grounded using an efficient ground line.
The installation must foresee a device enabled to disconnect the machine from the electric supply, furthermore,
a safety fuse of 2.5 A (delayed motor starting type) must be installed.
2.4 Hydraulic connection
The installation of the humidifier foresee the connection to the piping lines of water supply and drainage at the
proper points (Fig. 1.3 – Water supply 1/2” tube - Exhaust hole with fast connection
⅜
”).
The pipes that must be used are of type hard “rilsan” for drainage, while, for the supply, a 1/2” fit
is predisposed.
Drop separator
Drain system