About the menus described here:
See also the overview from page
▶
44.
Menu
6.1.4
14: Query door type
During initial start-up or after a factory reset, you can query
the set door type via menu 14.
To query the door type:
Select menu
1. 14 as described in section 6.
Press the
2. PRG button.
The set door type will be displayed as long as the PRG
button is pressed.
Menu
6.1.5
15 – 18: Operator light controlled by the
operator
The operator light is switched on as soon as the door starts
moving. After the door has stopped moving, the operator light
remains on for the set period (illumination period).
If menu 15 is activated, the operator light will not be switched
on once the door starts moving.
The illumination period for the operator light can be set using
menus 16 – 18.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.
Menu
6.1.6
19 – 21: Operator light controlled by
external control elements
The operator light can be switched on with an external control
element (e.g. hand transmitter or internal push button IT 3b,
PB 3) and remains on for the set period (illumination period).
If menu 19 is activated, the operator light cannot be switched
on with an external control element.
The illumination period for the operator light can be set using
menus 20 – 21. Menu 23 is also activated automatically.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.
6.1.7 Menu 22 – 29: Functions with additional print
If menu 22 is activated, the external light can be turned on and
off permanently. Not possible in combination with menu 23.
The operator light is always deactivated.
If menu 22 is activated, menu 19 is also automatically
activated ad menus 23 – 29 cannot be activated!
If menu 27 or 28 is activated and no pre-warning phase or
hold-open phase has been activated (menu 31 – 35, 41),
the relay does not function despite the activated menu.
Option relay HOR 1 is required to connect an external lamp
or warning light.
The universal adapter print UAP 1 can be used to control
further functions such as Open and Close limit switch
reporting, direction selection or operator light.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.
Menu 30
6.1.8
– 31: Pre-warning phase
Menu 30 deactivates the pre-warning phase. The door starts
moving immediately after a travel command.
If menu 31 is activated and a travel command is given, a
warning light connected to the option relay is illuminated for
5 seconds before the door starts moving. The pre-warning
phase is active in the Open and Close direction.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.
Menu 32
6.1.9
– 36: Automatic timer
With an automatic timer, the door is only opened with a travel
command. The door closes automatically after a set time and
the pre-warning phase have elapsed. If the door receives a
travel command while it is closing, the door will stop and open
again.
NOTES:
The automatic timer may/can only be activated within the
ō
scope of DIN EN 12453 if at least one additional safety
device (photocell) is connected besides the standard
power limit.
If the automatic timer is set (menus
ō
32 – 35), the pre-
warning phase (menu 31) and the photocell (menu 61) will
automatically be activated.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.
Menu
6.1.10
37 – 38: Hold-open phase functions
The time set for the automatic timer corresponds to the hold-
open phase for the door before it automatically closes.
If menu 37 is activated, the hold-open time is extended by an
impulse radio code, an external control element with impulse
function, the button
or a photocell.
If menu 38 is activated, the hold-open phase is cancelled by
an impulse radio code, external control element with impulse
function or the button
and the door closes immediately
after the pre-warning phase has elapsed.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.
Menu 41
6.1.11
– 42: Automatic timer from the partial
opening position
Not suitable for side sliding sectional doors!
NOTES:
The automatic timer may/can only be activated within the
ō
scope of DIN EN 12453 if at least one additional safety
device (photocell) is connected besides the standard
power limit.
If the automatic timer is set (menu
ō
41), the photocell
(menu 61) will automatically be activated as well. The
pre-warning phase (menu 31) will not be activated.
If menu 41 is activated, the door will automatically close after
1 hour.
Menu 42 deactivates the automatic timer from the partial
opening position.
To set the desired function:
Select the menu for the desired function as described in
▶
section 6.