Jandy AE-Ti Installation And Operation Manual - page 20
Page 18
3.
Press the Up or Down button to display
REMOTE. Press the MENU button.The SELECT
REMOTE OFF (default remote) appears, use the
Up or Down button to scroll through the Remote
options. When you reach HI-LO-COM, press the
MENU button to select the remote. Press POOL
or SPA to exit the Service Setup mode.
4.5.2
Connection to an AquaLink RS
Control System or Remote TSTAT
(2-Wire Connection)
4.5.2.1 Confi gure the AquaLink RS Control
System
1. Install
a
fi xed resistor, with a value of 2.2K
Ohms, in the solar sensor terminals #3 and #4 of
the green, 10-pin terminal bar of the AquaLink
RS Power Center (see Figure 13). (Resistor is
included with the Heat Pump.)
2.
Run the wires from the Heat Pump control panel
through the wiring conduit located on the outer
right hand side of the Heat Pump.
3.
In the AquaLink Power Center, connect the Heat
Pump to a standard relay, then connect the relay
to the solar pump output on the PCB. Set the time
to 11:59 PM; at 12:00 AM, the AquaLink RS
will auto-relabel Solar as Heat Pump. Otherwise,
the AquaLink RS will auto-relabel Solar as Heat
Pump within 24 hours.
4.
The Solar Button will activate the heat pump/
chiller and the Pool and/or Spa Heater Buttons will
activate the gas heater. In this manner the pool or
spa can be heated or chilled by the heat pump, the
gas heater or both.
4.5.2.2 Install the Remote TSTAT
1.
Turn off the power to both the pool/spa control
system and the heat pump unit.
2.
Remove the four (4) screws that attach the service/
access panel to the heat pump unit and the cover to
the junction box (See Figure 11).
3.
Run the wires from the pool/spa control system
into the conduit connection labeled “low voltage
connection”, located on the lower right hand side
of the heat pump (See Figure 11).
4.
Connect the wiring from the pool/spa control
system to the heat pump remote control terminal
(See Figure 12b).
5.
Restore power to the heat pump and the pool/spa
control system.
Figure 13. AquaLink RS to AE-Ti Heat Pump/Chiller Wiring
Gas Heater
Heat Pump/Chiller #2
Service/Wiring
Cover Panel
Standard
High
Voltage
Relay
Heat Pump/Chiller #1
Green- Enabled
Red- On
Gas Heater Connections
Terminals 1 and 2
Fireman's
Switch
From Fusible
Link
To Pressure
Switch
LED
will not
come on
for Heat
Pump
2.2K Ohms Resistor
in Solar Sensor
Terminals for Heat
Pump/Chiller
Low Voltage
Wiring to Low
Voltage Connector
on Heat Pump
Service/Wiring
Cover Panel
Connector for Low
Voltage Wires
Connector for Low
Voltage Wires
4 3 2 1
6 5 4 3 2 1
10 9 8 7 6 5 4 3 2 1
Battery
(9Volt)