Design and Function
Short Description
4.2 Short Description
The KaCool D is a decentralised unit for heating, cooling and
fi ltering air in hotels, offi ces and conference rooms, amongst
other places. Users can set a comfortable temperature for
themselves thanks to the effective and extremely quietly
operated fan.
Operating mode
The secondary air is drawn in to the middle section of the
casing. The air initially passes through the air intake grille to
the fi lter. This removes dust, for example, from the secondary
air and therefore protects the following components from
contamination. The air is drawn out by the fi lter and forced
through the copper/aluminium heat exchanger. The air is
cooIed or heated in the exchanger depending on the
temperature at which the medium fl ows through the heat
exchanger.
The air passes through the outlet air slats into the room. The
outlet air slats can be manually adjusted depending on the
desired air direction.
Condensation may be produced on the heat exchanger when
cooling with low water temperatures. This drips onto the heat
exchanger and falls into the condensation tray underneath.
The condensation accumulates in one corner. A fl oat switch
monitors the condensation level. The condensation pump is
activated when a a certain level is exceeded. A condensation
warning is issued if an even higher level is exceeded.
Valve kits, available as accessories, can be connected to the side
of the unit. The units are supplied with condensation trays that
can be installed below the valve kits. The condensation is
routed and drained through a prepared opening into the
condensation tray of the unit.