Kampmann KaCool D 1 Installation And Operating Instructions Manual - page 33
33
KaCool D
02.02.2017
Installation and Connection
Installation: Accessories
Installation: Accessories
Accessories: Fresh air connection, art. no. 325007000300
Primary air spigots for fresh air supply
Fresh air connection spigots (see Accessories) can be fi tted to
three of the four corners of the ceiling cassette. This enables
rooms to be supplied with a percentage of fresh air. The air
has to be cleaned on site with an appropriate air fi lter and be
routed to the cassette at a minimum temperature of 5°C.
Maximum fresh air volume per unit
Model
Air volume
1)
[m³ / h]
1
85
2
100
3
120
4
150
5
150
6
150
Installing the primary air spigot
Fresh air connection
1)
A maximum of 100m³/h can be fed in per corner / connecting spigot with models 1 to 3 and 50 m³/h with models 4 to 6.