Installation and Connection
Control overview
1 = Condensation level OK
2 = Condensation pump foot contact
3 = Condensation level too high, fault
4 = Heating valve 4-pipe, foot contact
5 = Cooling valve 2 / 4-pipe, foot contact
6 = Heating valve 4-pipe, foot contact
7 = Cooling valve actuation, 2 / 4-pipe
8 = Neutral wire, heating and cooling valve
9 = Neutral wire, thermostat
10 = Power supply to thermostat
L = Power supply 230 V/50 Hz
N = Neutral wire
V 3 = Maximum fan stage
V 2 = Medium fan stage
V 1 = Minimum fan stage
RL1 = 150 seconds from the liquid falling below
the lower level, pump on (Condensation
pump control)
RL2 = 150 seconds from the liquid falling below
the upper level, alarm on (Condensation
pump control)
J1.1
L
L
L
N
N
M
M
M
1 ~
M
1 ~
Z
NM
NM
M3
M7
M6
M2
M1
M4
NM
bn
sw
gnge
bl
C
1
4
LPC
RL1
RL2
T1.6
AL
SEC1
Condensation pump
Float switch
Fan
J1
J5
J2
J4
M5
J3
J1.2
CM
CM
V2
LM
C
2
5
8
3
6
9
L
7
10
N
NPC
J1.3
LM
V3
V1
V2
V3
V1
The cooling valve has to be routed via the
condensation alarm. The valve has to be closed
when the contact changes to fault.
AC fans, electromechanical model
Stand-alone unit, on-site control
EC fans, electromechanical model
Stand-alone unit, on-site control
1 = Condensation level OK
2 = Foot contact
Condensation
pump
3 = Condensation alarm
A+ = Signal input
Impedance < 68 KOhm
A- = Signal input
Impedance < 68 KOhm
L = Power supply
230 V / 50 Hz
N = Neutral wire
RL1 = 120 seconds from the
liquid falling below the
lower level, pump on
(Condensation pump
control)
RL2 = 120 seconds from the
liquid falling below the
upper level, alarm on
(Condensation pump
control)
The cooling valve has to be routed via the
condensation alarm. The valve has to be closed
when the contact changes to fault.
15V
Mains power supply:
230 / 50 Hz
(fuse provided by the
customer)
M2
L
N
A+
TP
TP
PE
U
V
W
TK
TK
PE
M
3 ~
BLAC
SEP
M3
RLS
RL2
top
bottom
M1
1
J3
J1
bn
or
ws
L
L
N
N
J1.1 J1.2 J1.3
LPC NPC
1
2
3
A-
X2
P+
P -
L
N
M
1 ~
Condensation pump
Float switch
U
V
W
EC fan
Control
0 – 10 V
1)
Condensation alarm
(potential-free)
Alarm
Pump is
enabled
Operation
RL1
0 – 10 V
GND
C
NC
NO
N
PE
L
1)
0 V: Off/ >1,5-10 V: On