KEB COMBIVERT F6 Instructions For Use Manual - Attention
4.2.2 Wiring diagram cooling system
This connection diagram serves only as an installation proposal and restores
no professional planning and design!
WRB
WRA
AFE
①
➃
➄
②
③
②
①
②
③
②
①
②
②
1
1/4
“
1
1/4
“
¾“
¾“
¾“
¾“
5/8“
5/8“
③
Housing V
Legend
WRA
Drive converter A
WRB
Drive converter B
①
Throttle valve adjustable 10 - 40 l/min
②
Ball valve/shut-off valve
③
Volume flow meter
④
forward
⑤
reverse
AFE
AFE filter; the values for falling pressure, volume flow and flow temperature can be taken from
the technical data sheet of the AFE filter.
Figure 4:
Wiring diagram cooling system
ATTENTION
►
Liquid cooling systems and other components in the cooling circuit
must be operated parallelly.
► Pay attention to flux direction and check tightness !
•
The min. volume flow depends on the total power loss.
•
Max. temperature difference (ΔT) between inlet and return flow 7 K.
•
A volume flow over 40 l/min increases the risk of erosion in the
liquid cooler.
• A discontinuous operation is not permitted, this leads to immediate
destruction of the dunit.
•
For further details on the AFE filter, please refer to the technical
data sheet of the filter.