KEB COMBIVERT F6 Instructions For Use Manual - page 62
6.2 electrical data 690 V mains voltage
Inverter size
33
37
Drive converter A (AFe)
Input rated voltage
U
V AC
600 / 690
Input voltage range
U
in
V AC
360…760 ±0 %
Mains frequency
F
Hz
48 - 63
Phases
3
Permitted mains forms
TN, TT
Max. supply imbalance
%
8
Max. permissible mains short-circuit
current
Icc
kA
50
Max. permissible mains fuse (F1)
1)
A AC
630 optional
required
Input rated power
S
in
kVA
600
980
Max. input power
P
in
kW
450
710
Supply / regenerative rated current
I
in
A AC
500
820
Max. short time current (E.OL) 30 s
I
OL
%
125
125
OC-tripping current (E.OC)
I
OC
%
150
150
Rated switching frequency
f
S
kHz
4
4
Voltage rise (10-90%)
du/dt
kV/μs
5
Drive converter b (Drive)
Output rated power
S
out
kVA
600
980
Max. output power
P
out
kW
450
710
Output rated current
I
out
A AC
500
820
Max. short time current (E.OL) 30 s
2)
I
OL
%
125
125
OC-tripping current
I
OC
%
150
150
Standstill current at 4 kHz
3)
I
dc
A DC
343
563
Output voltage
4)
U
in
V AC
0…Uin
Rated switching frequency
f
S
kHz
4
4
Max. switching frequency
5)
f
Smax
kHz
4
4
Output frequency
6)
f
out
Hz
0…max. 599
Min. frequency at continuous full load
f
min
Hz
3
Voltage rise (10-90%)
du/dt
kV/μs
5
Overload characteristic
(see annex A)
cable cross-section
Min. mains cable cross-section
mm²
2 x 120
1 x 240
2 x 240
Motor cable cross-section
7)
mm²
2 x 120
1 x 240
2 x 240
Max. motor cable length shielded
M
100
continued on the next page
62