7 Start-Up
7.1 Procedure for initial start-up
• The control boards can be put into operation via an external 24 V DC supply.
• This enables the pre-parameterization of the control boards without charging the DC
link of the drive converter.
• The communication with the converters can be established via the diagnostic inter-
faces of the control boards.
• This requires a PC and the corresponding software to parameterize the converters.
• The structure of the communication is described in the application manuals of the
control boards.
Information about the F5 control boards can be found
here.
Information about the F6 control boards can be found
here.
• The WRA (AFE) is factory pre-parameterized via download. No further settings need
to be made.
• Adjustments must only be made if the cabinet system is not operated at 690 V AC
voltage.
• Information can be found in the programming manual AFE housing V.
Note to further documentation.
ATTENTION
ThecoolantflowmustalwaysbestartedbeforestartingtheKEB
COMBIVERT.