Keba KeContact P20 Installation Manual - page 30
Other manuals for KeContact P20:
Installation Manual, User Manual
of
48
Installation
30 / 48
Example (supplement to the circuit diagram):
The switch contact can be used to switch off the KeContact P20 (disconnect the current) by
means of an overriding disconnect solution.
-
Q1…
Main circuit breaker
-
Q2…
Line circuit breaker + RCD circuit breaker
-
Q3…
Contactor/Relay
-
F1…
Current-limiting protective device
-
U1…
Undervoltage release
-
X2…
Switch contact output
4.4.5 Terminals [X1/X2] (except e-series)
Terminal
Terminals
The terminals for the enable input [X1] and the
switch contact output [X2] are designed as
spring-type terminals.
Terminal data:
- Cross-section (min.-max):
0.08
– 4 mm²
- AWG (min.-max):
28
– 12
- Stripping length:
8 mm
- Flathead screwdriver: 3,0 mm