In order to view the log, press the button" DIS", and then “DISARMED LOG”. A list will chronologically
show the operations and indications that have been made. To exit the disarmed log, press the button
“BACK”.
To view all the log, use the scroll up and down the button to move around the window. A description of
all the logs will be available at Appendix B.
ϯ͘ϱ
P.A MODE
The equipment / system EXEO, besides acting as a voice evacuation system, can function as a high-
performance public-address system, when a voice evacuation is not required.
To access the Paging menu, proceed as follows:
Press the shortcut button "P.A", the access control for users with level 2 will appear (see 2.3). To
return, press the "BACK" button. Once passed the access control, the level of access authorization, will
change to "Level 2" and access the menu, which contains the options: Zone volume setting, routing of
audio sources and advanced.
ϯ͘ϱ͘ϭ
ZONE VOLUME SETTING
The equipment/ system, allows adjustment of volumes for each zone. This setting can be independent
from the zone volume adjustment made to broadcast the voice message in emergency state, if it has
been previously configured (see 3.2.6). The adjustment of the zones is relative to the adjustment of the
output gain or audio outputs grouped in the zone (see 3.5.5).
To make this setting, from the PA menu window, click on the zone volume setting button "ZONES
VOLUME", the following window will appear:
Picture 30: P.A Menu Window
Page
27
sur
51
ĂͿ
ZONES BUTTONS
In the left half of the screen, the zones can be found. Press on the zones in which you want to set the
volume. If the progress indicator appears (see 2.2.6) use the scroll control to display the other zones. If
there is no selection, the setting is made on all zones of the system.
ďͿ
GAIN STEP SETTING BUTTON
The step setting buttons, allows the selection of the step increment / decrement to be performed when
you press on the volume adjustment buttons. You can select from the following values, pressing
consecutively: 1dB, 5dB, 10dB.
ĐͿ
MUTE BUTTON
The mute button allows a radical decrease of the volume of the zone / zones to a minimum. When the
mute is disabled, the zones will recover the volume they had before being silenced. If you turn the mute
button on a zone / zones which was not selected, there will be no setting on it.
ĚͿ
VOLUME INDICATOR
The volume indicator goes from -100dB to 0dB, minimum and maximum respectively zone volume. If a
zone is selected, the current volume level will be displayed, and will be updated while you make the
settings. If you have made a multiple selection, any value will be shown, until a setting is made. In this
case, only the setting made will be displaying.
ĞͿ
ROUTED SOURCE
This field will show the audio source routed to the selected zone.
ĨͿ
VOLUME ADJUSTMENT BUTTONS
The volume adjustment window has two buttons to adjust " +" and "- ", each time you press one of them,
it will be increased or decreased, as many decibels as the " Gain Step Setting" is displaying. To carry out
this setting, select the zone/zones on which you would like to perform the adjustment, change the value
of the volume, and confirm by pressing " OK".
To cancel, press the " BACK" button. If there is no selection of zone/zones, the settings will be applied to
all zones.
NOTE: If you make a multiple selection of zones, it is possible to apply a relative increase or decrease in
volume. The maximum value that can reach the group is determined by the zone, within the selected
group, which has the highest volume. So when it reaches the 0dB (maximum), or the set step is greater
than the difference between 0dB and the current value will not be allowed to continue to increase the
volume. The same happens in the case of the minimum volume.
Picture 31: Zones volume setting Window