Navien CH-180 Service manual - page 115
©Navien America Inc. 2010
CH series service Manual
113
Version 1.0
6.2. Measuring Gas Pressure Setting
6.2.1. How to Check Inlet Gas Pressure
Procedure to measure the inlet gas pressure:
THIS SECTION IS ONLY TO BE DONE BY A LICENSED
PROFESSIONAL
All Safety messages will refer to potential hazards. Precisely follow the
instructions to avoid the risk of injury.
1. Shut off the manual gas valve on the supply gas line.
2. Open a hot faucet. The unit should turn on and the gas in the gas pipe line
should purge. Leave the faucet on to keep the unit running until the unit shuts
down due to lack of gas supply. Then shut off the hot faucet.
3. Remove the screw for the pressure port located on the gas inlet of the boiler.
4. Connect a manometer to the pressure port and reset it to zero.
5. Re-open the manual gas valve. Check to see that there are no gas leaks.
6. Open multiple fixtures that have high flow rates (bathtub, showers, kitchen sink)
to ramp the boiler up to its maximum burn.
7. When the Navien boiler is at maximum burn, check the inlet gas pressure read
ing on the manometer; it should read between 6.0”~10.5” W.C for Natural gas
between 8.0”~13.5” W.C for Liquid Propane.
8. The maximum inlet gas pressure must not exceed the value specified by the
manufacturer and that the minimum value listed is for the purposes of input
adjustment.
Pressure test port on gas line
The Navien water heater cannot operate properly without sufficient inlet gas pressure
and volume. Below are instructions on how to check the inlet gas pressure.