PSA Products LIFESAVER LIFPE10 User Manual - page 3
3
Specification
Power: DC3V(CR123A) lithium battery (not replaceable)
Operating Current:
Alarm Volume: >85dB(A) at 3 meters.
Alarm Sensitivity: 0.09-0.17dB/m
Silence Time: approx. 10 minutes
Smoke Alarm Device Sound Pattern: ISO8201
Comply with Australian Standard: AS3786:2014
Installation
Recommended Locations
• Locate an alarm for each separate sleeping area in the
immediate vicinity of the bedrooms. Try to monitor the exit
path as the bedrooms are usually farthest from an exit. If
more than one sleeping area exit, locate additional alarms
in each sleeping area in the immediate vicinity bedrooms.
• Locate additional alarms to MONITOR any stairway as
stairways act like chimneys for smoke and heat.
• Locate at least one alarm on every floor level.
• Locate an alarm in every room where a smoker sleeps.
• Locate an alarm in every room where electrical
appliances are operated (i.e. portable heaters or
humidifiers).
• Locate an alarm in every room where someone sleeps
with the door closed. The closed door may prevent an
alarm not located in that room from waking the sleeper.
• Smoke, heat and other combustion products rise to the
ceiling and spread horizontally. Mounting the alarm on the
ceiling in the center of the room places it closest to all
points in the room. Ceiling mounting is preferred in
ordinary residential construction.
• For mobile home installation select location carefully to
avoid thermal barrier that may form at the ceiling. For
more details see Mobile Home Installation (Page 5).