• When mounting alarms on the ceiling locate it at least
300mm away from the side wall and 300mm away from
any corner. (see diagram)
• When mounting alarms on a wall, use the inside wall. The
recommended position is between 300mm and 500mm
off the ceiling. (see diagram)
• NOTE: The performance of smoke alarms mounted on
walls is unpredictable and this mounting position is
not recommended when ceiling mounting can be
implemented.
• When mounting the alarm at the apex of a sloping ceiling
it should be located at least 500mm away from the apex
but should not exceed 1500mm (see diagram).
• Locate smoke alarm at both ends of a bedroom hallway
or large room if the hallway or room is more than 9m long.
• Do not locate smoke alarms in kitchen areas due to
potential nuisance alarms from cooking fumes.
Smoke alarm with Remote Test & Hush card
Remote Test & Hush Plate
Connection diagram between smoke alarm and Remote Test & Hush plate