Quincy Compressor QED 1050 Instruction And Maintenance Manual - page 19
Reference
Name
102
Condensate separator
201
Non-return valve
202
Air-cooled condenser (air-cooled version)
203
Fan blower (air-cooled version)
*)
204
Thermostatic expansion valve
205
Pressure shut-down switch
206
Refrigerant dryer/filter
207
Liquid separator
208
Hot-gas by-pass valve
209
Refrigerant compressor
210
Solenoid valve
211
Sight-glass
212
Flow switch
213
Temperature switch
214
Pressure sensor
(air-cooled version)
301
Cubicle
401
Automatic drain
(1)
Air
(2)
Refrigerant
(3)
Drain
(4)
Water
(5)
Mechanical link
(6)
Electric power
(7)
Electric signal
(8)
Enclosure for several components assembled in one unit
*)
Second fan blower is installed on QED 1050
Description
Compressed air enters heat exchanger (101a) and is cooled by the outgoing, cold, dried air. Water in the
incoming air starts to condense. The air then flows through heat exchanger/evaporator (101b) where the
refrigerant evaporates causing the air to be further cooled to close to the evaporating temperature of the
refrigerant. More water in the air condenses. The cold air then flows through separator (102) where all the
condensate is separated from the air.
The condensate collects in the Electronic Water Drain (EWD) (401) and is automatically drained. The cold,
dried air flows through heat exchanger (101a), where it is warmed up by the incoming air to approx. 5 ˚C (9
˚F) below the incoming air temperature.
Condensation in the air net cannot occur unless the air is cooled to below the pressure dew-point indicated
on the control panel.