Quincy Compressor QED 1050 Instruction And Maintenance Manual - 4.4
4.4
Electric cable size and fuses
Important
Local regulations remain applicable if they are stricter than the values proposed.
For 60 Hz dryers, the settings of the main fuses below are according to CSA standards C22.2
Nos. 0; 0.4; 0.5; 0.12; 14; 68 and UL508. The cable size is valid for cable 90 ˚C (194 ˚F) at
an ambient temperature of 40 ˚C (104 ˚F).
Fuses
Dryer
Supply voltage
Maximum fuses, recommended type: (CSA)
Class HRC Form II/(UL) Class K5 or RK5
(customer's installation)
QED 650
460 V
3 x 20 A
QED 850
460 V
3 x 20 A
QED 1050
460 V
3 x 25 A
Electrical cable size
60 Hz CSA/UL - 40 ˚C (104 ˚F) variant
Dryer
Supply voltage
Supply cable section, recommended
QED 650
460 V
3 X AWG 12 + AWG 12
QED 850
460 V
3 X AWG 12 + AWG 12
QED 1050
460 V
3 X AWG 10 + AWG 10