is charging and this level is crossed certain actions will be performed automatically.
UPS Recovery Power Threshold
The powered outlets and outlets marked as AlwaysOn with respective power
consumptions below the recovery power threshold (in W) will be power cycled when the
UPS is running on mains power and the battery level goes above the Battery Recovery
Threshold (assuming that the battery level dropped below the Battery Emergency
Threshold first). For more information see the Rules chapter.
SNMP Warning
o Checked: SNMP traps will be sent when:
UPS Communication status changes
UPS switches between battery or mains
UPS Emergency Threshold is crossed
UPS Recovery Threshold is crossed
o Unchecked: No SNMP traps are sent
To enable the EnergySwitch to perform actions based on the UPS Integration data please also
refer to the Agent Communication chapter.
Rules
If both UPS Integration is enabled and Agent Communication is correctly configured the
EnergySwitch will perform automated actions according to strict pre-defined rules (based on
battery level, UPS status, etc.).
Please review the following rules and actions carefully to avoid unexpected behavior.
1. When the EnergySwitch boots, communication with the UPS is OK and the Battery Level
is above the UPS Recovery Threshold the outlets will be powered as configured by the
user.
2. When the EnergySwitch boots, communication with the UPS is OK and the Battery Level
is below the UPS Recovery Threshold only outlets marked with Prevent Outlet
Shutdown (see the EnergySwitch Configuration chapter) will be powered.
3. When the EnergySwitch boots and communication with the UPS fails, only outlets
marked with Prevent Outlet Shutdown will be powered.
4. When the UPS is running on battery and the Battery Level drops below the UPS
Emergency Threshold the EnergySwitch will send a shutdown command to all associated
agents.
5. When the communication with the UPS fails for 5 minutes a shutdown command is sent
to all associated agents of powered outlets.
6. When the UPS switches from mains to battery power while the Battery Level is below
the UPS Emergency Threshold a shutdown command is sent to all associated agents of
powered outlets.