WARninG!
Useofanappropriatelysizedexternalfuseasdescribedaboveismandatoryto
provide safety against fire hazard due to accidental short circuit in the battery
wires.PleasenotethattheDCsidefuse(s)insidetheunitaredesignedtopro-
videprotectiontotheinternalcomponentsoftheinverter.ThesefuseswillNoT
blow if there is a short circuit along the length of wires connecting the battery
and the inverter.
Recommended Sizes of Wires and external Fuses
Thefollowingsizesofwiresandexternalfusesarerecommended.Thedistanceof3ft./
6 ft. / 10 ft. is the distance between the battery and the inverter. The running length of
routing of the wire should be considered if the wiring run is not straight but circuitous.
The recommended size of wires will limit the voltage drop to 2% of the nominal battery
voltage(0.24Vfor12Vbatteryand0.48Vforthe24Vbattery)
Thelengthofthewireforcalculatingvoltagedrophasbeentakenas2timesthe
distance between the inverter and the battery assuming that 2 lengths of wires (one
PositiveandoneNegative)areusedfortheconnection.DCresistancevaluesarebased
onuncoated,strandedcopperconductorsatatemperatureof75°C.Thistemperatureis
typical of operating power circuits.
ModelNo.
Maximum
DCinput
current at
rated output
power
Size of Wire
Minimum
current
rating of
external
fuse
recommended
SAMLEX
DCInstallation
Kit*
3 ft.
6 ft.
10 ft.
PST-200S-12E
240A
AWG#1
AWG#3/0
AWG#4/0
240A
DC-2500-KIT
PST-200S-24E
120A
AWG#6
AWG#4
AWG#2
120A
DC-2000-KIT
PST-150S-12E
200A
AWG#2
AWG#2/0
AWG#4/0
200A
DC-2000-KIT
PST-150S-24E
100A
AWG#8
AWG#4
AWG#2
100A
DC-1000-KIT
PST-100S-12E
160A
AWG#3
AWG#1/0
AWG#3/0
160A
DC-2000-KIT
PST-100S-24E
80A
AWG#8
AWG#6
AWG#4
80A
DC-1000-KIT
PST-60S-12E
80A
AWG#6
AWG#3
AWG#1
80A
DC-1000-KIT
PST-60S-24E
40A
AWG#12
AWG#10
AWG#6
40A
DC-1000-KIT
*
ManufacturedbySamlexAmerica,Inc.(contains2wiresandfuse)