Powering on the Loads
Aftertheinverterisswitchedon,ittakesafinitetimetobecomereadytodeliverfull
power.Hence,alwaysswitchontheload(s)afterafewsecondsofswitchingonthe
inverter.Avoidswitchingontheinverterwiththeloadalreadyswitchedon.Thismay
prematurely trigger the overload protection.
Whenaloadisswitchedon,itmayrequireinitialhigherpowersurgetostart.Hence,if
multipleloadsarebeingpowered,theyshouldbeswitchedononebyonesothatthe
inverter is not overloaded by the higher starting surge if all the loads are switched on at
once.
Switching the inverter on/oFF
Beforeswitchingontheinverter,checkthatalltheACloadshavebeenswitchedoff.The
oN/offswitch(1)onthefrontpaneloftheinverterisusedtoswitchonandswitchoff
theinverter.Thisswitchoperatesalowpowercontrolcircuitry,whichinturncontrolsall
the high power circuitry.
!
cAUtion!
Please note that the oN/off switch is not switching the high power battery
inputcircuit.PartsoftheDCsidecircuitwillstillbealiveevenwhentheswitch
is in the offposition.Hence,disconnecttheDCandACsidesbeforeworking
on any circuits connected to the inverter.
Whentheinverterisswitchedon,theLEDindicator(2,figs.6.1,6.2,6.3)willturn
GREEN.ThisLED
indicatesthattheinverterisoperatingnormally.Undernormaloperatingconditions,
ACoutputvoltagewillnowbeavailableattheACoutlet(5).
SwitchontheACload(s).TheGREENLED(2)shouldremainlightedfornormalopera-
tion of the load.
temperature controlled cooling Fan
The cooling fan is thermostatically controlled. Temperature of a critical hot spot inside
the inverter is monitored to activate the fan and the over temperature shut-down.
Whenthetemperatureofthishotspotreaches48°C,thefanisswitchedoN. The fan
will be automatically switched offoncethehotspotcoolsdownto42°C.Pleasenote
that the fan may not come on at low loads or if the ambient temperature is cooler. This
is normal.