Wacker Neuson RCE Operator's Manual - page 47
RCE
Technical data
Operator’s manual
47
12.4
Extension cable
Only use permitted extension cables, see chapter Safety.
Refer to the following table for the required cross-section area of the
extension cable:
Note:
Refer to the nameplate or the chapter Technical data (via the item
number) for the type designation and voltage rating of your machine.
WARNING
Electrical voltage.
Injuries from electrocution.
f Check power cable and extension cable for signs of damage.
f Only use extension cables for which grounded conductors are connected to
the plug and the coupling (only for machines of class rating I, see chapter
Technical Data).
Machine
Voltage
[V]
Extension
[m]
Cross-section
area of cable
[mm
2
]
RCE-16
115
< 33
1.5
< 54
2.5
< 86
4
< 128
6
120
< 34
1.5
< 56
2.5
< 90
4
< 133
6
230
< 103
1.5
< 150
2.5