4 INVERTER PROGRAMMING
Next, only the CFW701 frequency inverter parameters related to the BACnet communication will be presented.
4.1
SYMBOLS FOR THE PROPERTIES DESCRIPTION
RO
Read-only parameter
CFG
Parameter that can be changed only with a stopped motor
Net
Parameter visible on the HMI if the inverter has the network interface installed – RS232, RS485, CAN,
Anybus-CC, Profibus – or if the USB interface is connected
Serial
Parameter visible on the HMI if the inverter has the RS232 or RS485 interface installed
P0105 – 1
ST
/2
ND
RAMP SELECTION
P0220 – LOCAL/REMOTE SELECTION SOURCE
P0221 – SPEED REFERENCE SELECTION – LOCAL SITUATION
P0222 – SPEED REFERENCE SELECTION – REMOTE SITUATION
P0223 – FORWARD/REVERSE SELECTION – LOCAL SITUATION
P0224 – RUN/STOP SELECTION – LOCAL SITUATION
P0225 – JOG SELECTION – LOCAL SITUATION
P0226 – FORWARD/REVERSE SELECTION – REMOTE SITUATION
P0227 – RUN/STOP SELECTION – REMOTE SITUATION
P0228 – JOG SELECTION – REMOTE SITUATION
These parameters are used in the configuration of the command source for the CFW701 frequency inverter local
and remote situations. In order that the device be controlled through the BACnet interface, the options ‘serial’
available in these parameters, must be selected.
The detailed description of these parameters is found in the CFW701 programming manual.
P0308 – SERIAL ADDRESS
Range:
0 to 255
Default: 1
Properties:
CFG
Access groups via HMI:
NET
Description:
It allows programming the address used for the inverter serial communication. It is necessary that each device in
the network has an address different from all the others. The valid addresses for this parameter depend on the
protocol programmed in P0312:
P0312 = 2 (Modbus RTU)
→ valid addresses: 1 to 247.
P0312 = 3 (BACnet MS/TP)
→ valid addresses: 0 to 254.
P0312 = 4 (N2)
→ valid addresses: 1 to 255.
NOTE!
The equipment must be initialized when the serial address is changed.