WEG bacnet CFW701 User Manual - page 27
BACnet Object Modeling
CFW701 | 27
5.1.5 BINARY OUTPUT (BOUT) OBJECT
It represents a physical digital output that can have its status changed by the controller. CFW701 BINARY
OUTPUT type objects are described in the Table 5-6.
Table 5-6: BINARY OUTPUT objects
Object
Identifier
Object name
Description
Active/inactive
Access
type
BOUT0
DO1 Value
DO1 digital output
(P0695 parameter BIT 0)
ON/OFF
C
BOUT1
DO2 Value
DO2 digital output
(P0695 parameter BIT 1)
ON/OFF
C
BOUT2
DO3 Value
DO3 digital output
(P0695 parameter BIT 2)
ON/OFF
C
BOUT3
DO4 Value
DO4 digital output
(P0695 parameter BIT 3)
ON/OFF
C
BOUT4
DO5 Value
DO5 digital output
(P0695 parameter BIT 4)
ON/OFF
C
5.1.6 BINARY VALUE (BV) OBJECT
They represent system control parameter bits that can be read, written or commanded by the controller.
CFW701 BINARY VALUE type objects are described in the Table 5-7, Table 5-8 and Table 5-9.
Table 5-7: Parameter P0680 BINARY VALUE objects
Object
Identifier
Object name
Description
Unit
Access
type
BV0
Reserved
BV1
Reserved
BV2
Fire Mode
Fire Mode
(P0680 parameter BIT 2)
ON/OFF
R
BV3
Bypass
Bypass
(P0680 parameter BIT 3)
ON/OFF
R
BV4
Active Quick Stop
Active Quick Stop
(P0680 parameter BIT 4)
ON/OFF
R
BV5
2nd Ramp Select
Second ramp
(P0680 parameter BIT 5)
ON/OFF
R
BV6
In configuration mode
Configuration mode
(P0680 parameter BIT 6)
ON/OFF
R
BV7
Alarm condition
Alarm
(P0680 parameter BIT 7)
ON/OFF
R
BV8
Ramp Enabled (RUN)
Enabled Ramp
(P0680 parameter BIT 8)
ON/OFF
R
BV9
General Enabling active
General enable
(P0680 parameter BIT 9)
ON/OFF
R
BV10
Speed Direction
Speed direction
(P0680 parameter BIT 10)
ON/OFF
R
BV11
JOG
JOG
(P0680 parameter BIT 11)
ON/OFF
R
BV12
LOC/REM
LOC/REM
(P0680 parameter BIT 12)
ON/OFF
R
BV13
Undervoltage
Undervoltage
(P0680 parameter BIT 13)
ON/OFF
R
BV14
Reserved
BV15
Fault condition
Fault
(P0680 parameter BIT 15)
ON/OFF
R
Table 5-8: MBOX BINARY VALUE objects
Object
Identifier
Object name
Description
Active/inactive
Access
type
BV100
MBOX read
Command to read the contents of the
parameter specified in the ANV100 object.
ON/OFF
W
BV101
MBOX write
Command to write the contents specified in
the ANV101 object in the parameter
specified in the ANV100 object.
ON/OFF
W
The section 5.1.8 describes the MBOX operation.