WEG bacnet CFW701 User Manual - page 20
Inverter Programming
CFW701 | 20
This parameter is mapped in the ANV17 object.
P0695 – DIGITAL OUTPUT SETTING
Range
0000h to 001Fh
Default: 0000h
Properties:
-
Access groups via HMI:
NET
Description:
It allows the control of the digital outputs by means of the network interfaces (Serial, CAN, etc.). This parameter
cannot be changed via HMI.
Each bit of this parameter corresponds to the desired value for one digital output. In order to have the
correspondent digital output controlled according to this content, it is necessary that its function be
programmed for “P0695 Content” at parameters P0275 to P0279.
Bits
15 to 5
4
3
2
1
0
Function
R
es
er
ved
D
O
5 s
et
tin
g
D
O
4 s
et
tin
g
D
O
3 s
et
tin
g
D
O
2 s
et
tin
g
D
O
1 s
et
tin
g
Table 4.5: P0695 parameter bit functions
Bits
Values
Bit 0
DO1 setting
0: DO1 output open.
1: DO1 output closed.
This bit is mapped in the BOUT0 object
Bit 1
DO2 setting
0: DO2 output open.
1: DO2 output closed.
This bit is mapped in the BOUT1 object
Bit 2
DO3 setting
0: DO3 output open.
1: DO3 output closed.
This bit is mapped in the BOUT2 object
Bit 3
DO4 setting
0: DO4 output open.
1: DO4 output closed.
This bit is mapped in the BOUT3 object
Bit 4
DO5 setting
0: DO5 output open.
1: DO5 output closed.
This bit is mapped in the BOUT4 object
Bits 5 to 15
Reserved
P0696 – VALUE 1 FOR ANALOG OUTPUTS
P0697 – VALUE 2 FOR ANALOG OUTPUTS
Range:
-32768 to 32767
Default: 0
Properties:
-
Access groups via HMI:
NET
Description:
They allow the control of the analog outputs by means of network interfaces. These parameters cannot be
changed via HMI.
The value written in these parameters is used as the analog output value, providing that the function for the
desired analog output be programmed for “P0696 / P0697 value”, at the parameters P0251, P0254.