WEG bacnet CFW701 User Manual - page 17
Inverter Programming
CFW701 | 17
Bit 4
Active quick stop
0: The fast stop command is not active.
1: The drive is executing the fast stop command.
This bit is mapped in the BV4 object
Bit 5
Second ramp
0: The drive is configured to use the first ramp values, programmed in P0100 and P0101, as the motor
acceleration and deceleration ramp times.
1: The drive is configured to use the second ramp values, programmed in P0102 and P0103, as the motor
acceleration and deceleration ramp times.
This bit is mapped in the BV5 object
Bit 6
In configuration mode
0: The drive is operating normally.
1: The drive is in the configuration mode. It indicates a special condition during which the drive cannot be
enabled:
Executing the self-tuning routine
Executing the oriented start-up routine
Executing the HMI copy function
Executing the flash memory card self-guided routine
There is a parameter setting incompatibility
There is no power at the drive power section
This bit is mapped in the BV6 object
Bit 7
Alarm condition
0: The drive is not in alarm condition.
1: The drive is in alarm condition.
Note: The alarm number can be read by means of the parameter P0048 – Present Alarm.
This bit is mapped in the BV7 object
Bit 8
Motor Running
0: The motor is stopped.
1: The drive is running the motor at the set point speed, or executing either the acceleration or the
deceleration ramp.
This bit is mapped in the BV8 object
Bit 9
Active General Enable
0: General Enable is not active.
1: General Enable is active and the drive is ready to run the motor.
This bit is mapped in the BV9 object
Bit 10
Speed direction
0: The motor is running in the reverse direction.
1: The motor is running in the forward direction.
This bit is mapped in the BV10 object
Bit 11
JOG
0: Inactive JOG function.
1: Active JOG function.
This bit is mapped in the BV11 object
Bit 12
LOC/REM
0: Drive in Local mode.
1: Drive in Remote mode.
This bit is mapped in the BV12 object
Bit 13
Undervoltage
0: No Undervoltage.
1: With Undervoltage.
This bit is mapped in the BV13 object
Bit 14
This bit is mapped in the BV14 object
Bit 15
Fault condition
0: The drive is not in a fault condition.
1: The drive has detected a fault.
Note: The fault number can be read by means of the parameter P0049 – Present Fault.
This bit is mapped in the BV15 object
P0681 – MOTOR SPEED IN 13 BITS
Range:
- 32768 to 32767
Default: -
Properties:
RO
Access groups via HMI:
NET
Description:
It allows monitoring the motor speed. This word uses 13-bit resolution with signal to represent the motor
synchronous speed: