WEG bacnet CFW701 User Manual - page 18
Inverter Programming
CFW701 | 18
P0681 = 0000h (0 decimal)
→ motor speed = 0
P0681 = 2000h (8192 decimal)
→ motor speed = synchronous speed
Intermediate or higher speed values in rpm can be obtained by using this scale. E.g. for a 4 pole motor and
1800 rpm of synchronous speed if the value read is 2048 (0800h), then, to obtain the speed in rpm one must
calculate:
8192 => 1800 rpm
2048 => Speed in rpm
Speed in rpm = 1800
× 2048
8192
Speed in rpm = 450 rpm
Negative values in this parameter indicate that the motor is running in the reverse direction.
This parameter is mapped in the ANV16 object.
P0682 – SERIAL CONTROL WORD
Range:
0000h to FFFFh
Default: 0000h
Properties:
-
Access groups via HMI:
NET
Description:
It is the device BACnet interface control word. This parameter can only be changed via serial interface. For the
other sources (HMI, etc.) it behaves like a read-only parameter.
In order to have those commands executed, it is necessary to program the equipment to be controlled via
serial. This programming is achieved by means of parameters P0105 and P0220 to P0228.
Each bit of this word represents a command that can be executed.
Bits
15
14
13
13 to 8
7
6
5
4
3
2
1
0
Function
E
xt
er
nal
P
ID
co
nt
ro
ller
2
E
xt
er
nal
P
ID
co
nt
ro
ller
1
Mai
n
P
ID
co
nt
ro
ller
R
es
er
ved
Fau
lt r
es
et
Q
ui
ck
s
to
p
S
eco
nd
ramp
LO
C
/RE
M
JOG
S
peed
d
irect
io
n
G
en
er
al
en
ab
le
R
un/
S
to
p
Table 4.4: P0682 parameter bit functions
Bits
Values
Bit 0
Run/Stop
0: It stops the motor with deceleration ramp.
1: The motor runs according to the acceleration ramp until reaching the speed reference value.
This bit is mapped in the object BV16
Bit 1
General enable
0: It disables the drive, interrupting the supply for the motor.
1: It enables the drive allowing the motor operation.
This bit is mapped in the object BV17
Bit 2
Speed direction
0: To run the motor in a direction opposed to the speed reference.
1: To run the motor in the direction indicated by the speed reference.
This bit is mapped in the object BV18
Bit 3
JOG
0: It disables the JOG function.
1: It enables the JOG function.
This bit is mapped in the object BV19
Bit 4
LOC/REM
0: The drive goes to the Local mode.
1: The drive goes to the Remote mode.
This bit is mapped in the object BV20