WEG bacnet CFW701 User Manual - page 26
BACnet Object Modeling
CFW701 | 26
ANV8
Internal Air Temp
Temperature of the internal air – P0034
°C
R
ANV9
Time Powered
Number of inverter powered hours – P0042
H
R
ANV10
Time Enabled
Number of inverter enabled hours – P0043
H
R
ANV11
kWh Output Energy
Counter of the output KWh – P0044
H
R
ANV12
Present Alarm
Present alarm – P0048
-
R
ANV13
Present Fault
Present fault – P0049
-
R
ANV14
Acceleration Time
Acceleration time – P0100
s
C
ANV15
Deceleration Time
Deceleration time – P0101
s
C
ANV16
Speed in 13 bits
Motor speed in 13 bits - P0681
%
R
ANV17
Serial/USB Speed Ref.
Speed reference via serial – P0683
-
C
ANV18
SoftPLC Parameter 1012
SoftPLC Parameter
-
C
ANV19
SoftPLC Parameter 1013
SoftPLC Parameter
-
C
ANV20
SoftPLC Parameter 1025
SoftPLC Parameter
-
C
ANV21
Automatic Setpoint main PID
Automatic Setpoint main PID – P1011
bar
3
C
ANV22
Manual Setpoint main PID
Manual Setpoint main PID – P1014
%
C
ANV23
Feedback main PID
Feedback main PID – P1015
bar-
3
R
ANV24
Main PID output
Main PID output – P1016
%
R
ANV25
Automatic Setpoint external PID 1
Automatic Setpoint external PID 1 – P1060
°C
3
C
ANV26
Manual Setpoint external PID 1
Manual Setpoint external PID 1 – P1061
%
C
ANV27
Feedback external PID 1
Feedback external PID 1 – P1062
°C
3
R
ANV28
External PID 1 output
External PID 1 output – P1063
%
R
ANV29
Automatic Setpoint external PID 2
Automatic Setpoint external PID 2 – P1080
%
3
C
ANV30
Manual Setpoint external PID 2
Manual Setpoint external PID 2 – P1081
%
C
ANV31
Feedback external PID 2
Feedback external PID 2 – P1082
%
3
R
ANV32
External PID 2 output
External PID 2 output – P1083
%
R
ANV100
MBOX parameter
MBOX parameter
W/R
ANV101
MBOX data
MBOX data
W/R
The CFW701 programming manual presents the detailed description of each parameter.
MBOX
The section 5.1.8 describes the MBOX operation.
5.1.4 BINARY INPUT (BIN) OBJECT
It represents a physical digital input that can have its status read by the controller. CFW701 BINARY INPUT type
objects are described in the Table 5-5.
Table 5-5: Parameter P0012 BINARY INPUT objects
Object
Identifier
Object name
Description
Active/
inactive
Access
type
BIN0
DI1 Status
DI1 digital input status
(P0012 parameter BIT 0)
ON/OFF
R
BIN1
DI2 Status
DI2 digital input status
(P0012 parameter BIT 1)
ON/OFF
R
BIN2
DI3 Status
DI3 digital input status
(P0012 parameter BIT 2)
ON/OFF
R
BIN3
DI4 Status
DI4 digital input status
(P0012 parameter BIT 3)
ON/OFF
R
BIN4
DI5 Status
DI5 digital input status
(P0012 parameter BIT 4)
ON/OFF
R
BIN5
DI6 Status
DI6 digital input status
(P0012 parameter BIT 5)
ON/OFF
R
BIN6
DI7 Status
DI7 digital input status
(P0012 parameter BIT 6)
ON/OFF
R
BIN7
DI8 Status
DI8 digital input status
(P0012 parameter BIT 7)
ON/OFF
R
BIN8
Reserved
BIN9
Reserved
BIN10
Reserved
BIN12
Reserved
BIN13
Reserved
BIN14
Reserved
BIN15
Reserved
3
The object unit can be defined by the user according to the application.