WEG SSW-08 User Manual - page 27
3
Installation and Connection
22 | SSW-08
NOTE!
It’s necessary to program the digital input DI2 for the three-wire command function.
Refer to item 4.10.
NOTE!
The RL1 shall be set to the “No fault” function. Refer to item 4.12.
3.3.3 Recommended Set-up with Command via Two-wire Digital Inputs and Direction
of Rotation
P220 = 1
P230 = 1
P263 = 1 (DI1 = Start/Stop two
wires)
P265 = 4 (DI3 = Rotation Direction)
P277 = 4 (RL1 = FWD/REV - K1)
P278 = 4 (RL2 = FWD/REV - K2)
Refer to notes in item 3.3
24
23
14
13
DI3
RL1
RL2
T1
P E
R
S
T
K1
K2
K2
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
Figure 3.12: Recommended Set-up with Command via Two-wire Digital Inputs and Direction of Rotation
NOTE!
To program the parameters shown above, is necessary the use of keypad or serial
communication. See the Programming Manual for more information.