WEG SSW-08 User Manual - page 55
8
Technical Characteristics
50 | SSW-08
8.3 POWER DATA
Power Supply Power Voltage (R/1L1, S/3L2, T/5L3)
(220 to 575) Vac (-15 % to +10 %), or (187 to 632) Vac
Frequency
(50 to 60) Hz (±10 %), or (45 to 66) Hz
Capacity
Maximum number of starts per hour
(without ventilation)
10 (1 every 6 minutes; models from 17 A to 30 A and
255 A to 412 A)
3 (1 every 20 minutes; models from 45 A to 200 A)
Maximum number of starts per hour
with optional ventilation Kit
10 (1 every 6 minutes; models from 45 A to 200 A)
Start cycle
3 x In of the SSW-08 during 20 seconds
Thyristors (SCRs)
Reverse voltage with 1600 V maximum peak
Overvoltage category
III (UL508/EN61010)
8.4 ELECTRONICS AND PROGRAMMING DATA
Power Supply Control voltage
Connector (A1, A2)
(110 to 240) Vac (-15 % to +10 %), or (94 to 264) Vac, models from
17 A to 200 A
(110 to 130) Vac or (208 to 240) Vac (-15 % to +10 %) models from
255 A to 412 A.
Frequency
(50 to 60) Hz (±10 %), or (45 to 66) Hz
Consumption
15 VA models from 17 A to 200 A
45 VA Continuos
530 VA additional during by-pass Closing (models from 255 A to 412 A).
Control
Method
Voltage ramp;
Current limitation.
Inputs
Digitals
3 Isolated digital inputs;
Minimum upper level: 93 Vac;
Maximum lower level: 10 Vac;
Maximum voltage: 264 Vac;
Input current: 1.1 mA @ 220 V;
Programmable functions.
Outputs
Relay
2 relays with NO contacts, 240 Vac, 1 A, and programmable functions.
Safety
Protections
Overcurrent;
Phase loss;
Inverted phase sequence;
Heatsink overtemperature;
Motor overload;
External fault;
Open By-pass contact;
Closed By-pass contact;
Overcurrent before By-pass;
Stall;
Frequency out of range;
Electronic supply undervoltage.