Baker D30R User Manual - page 25
12/3/2009 | 71-022 V6
D30R
25
Current
Leakage
Measured
Voltage
Applied
IR
=
4
Principles and theory of DC testing
Principles of DC testing
High voltage DC testing of electric motors is performed in order to determine the integrity of
the ground wall insulation system of a motor’s coil. The ground wall insulation system
consists of the wire’s insulation, slot liner insulation, wedges, varnish, and sometimes, phase
paper.
There are three types of DC tests performed by Baker test instruments:
Megohm
tests,
HiPot
tests, and
PI
tests. Each type of test is designed to answer a specific question regarding
the properties of or the integrity of the ground wall insulation system. There is also a
Stepped HiPot
test that can be performed with Baker testers. A brief discussion on each of
these tests follows below.
Before going further the meaning of “HiPot test” needs to be discussed. The phrase “HiPot
test” is used to describe the general idea of high voltage testing as well as to describe a
specific type of high voltage insulation stress test. One must differentiate between the concept
HiPot testing and the specific HiPot test based on the context of the discussion.
To perform any of the DC Tests, the motor’s windings are isolated from ground, the red test
leads from the Baker Tester are connected to the motor’s three phase coils and the black test
lead is connected to the motor’s steel core/frame. The output voltage on the red test leads is
raised to a predetermined test voltage and the leakage current flowing from the motor’s coils,
through the ground wall insulation, to the motor frame is measured. The Digital Tester then
calculates the resulting insulation resistance (IR) using Ohm’s law.
The
Megohm Test
consists of applying a DC voltage to the windings of a machine after first
isolating the winding from ground. The test lead selector switch makes all test lead
connections. The test voltage is usually chosen to be at or near the operating voltage of the
machine (see IEEE 43). Recommended test voltages can be found in the previous chapter
titled “Recommended Test Sequence, Voltages and Applicable Standards”.
The intended purpose of the Megohm test is to make an accurate measurement of the
insulation resistance of the ground wall insulation. The insulation resistance, abbreviated IR, is
a function of many variables: the physical properties of the insulating material, temperature,
humidity, contaminants etc. The IR value is calculated using Ohm’s law – the applied voltage
is divided by the measured leakage current. This leakage current is that current which is
actually able to pass from the winding through the ground wall insulation to the motor’s steel
core
plus
any surface leakage currents. The surface leakage currents flow through moisture
or contaminants on the surface of the insulation. To accurately determine the insulation
resistance, the surface leakage must be reduced to an inconsequential level.
The insulation resistance is a function of many variables: the physical properties of the
insulating material, temperature, humidity, contaminants on the surface of the winding’s
insulation, etc. The effects of temperature can be compensated for by converting the IR value
to a standard temperature 40
o
C as shown later in this chapter. The effects of humidity and
contaminants can not be readily taken into account. Good judgment must be used when
analyzing IR values from motors that may be wet, dirty, loaded with carbon dust, etc.