Eclipse EC-P50 Installation Manual - page 22
22
P0016-LI-03.01
2. Area Options
This section covers programming of the arming modes, timers
and options for each of the 5 areas.
Area Timers
Each arming mode has its own set of timers that are used to
control various delays during arming, disarming and in alarm.
Locations:
2101
to
2107
Area 1: Timers 01 to 07.
2201
to
2207
Area 2: Timers 01 to 07.
2301
to
2307
Area 3: Timers 01 to 07.
2401
to
2407
Area 4: Timers 01 to 07.
2501
to
2507
Area 5: Timers 01 to 07.
Entry Mode:
Number Entry (see page 18).
01 Exit
Delay
When the Arming Mode is configured as Timed or deferred, this
timer sets the delay between the user initiating the exit procedure
and the system actually arming.
02 Entry 1 Delay
When the system is armed, activation of a “Final Exit 1” zone will
start the entry 1 delay timer, this allows the user time to access
the remote keypad and disarm the system.
03 Entry 2 Delay
When the system is armed, activation of a “Final Exit 2” zone will
start the entry 2 delay timer, this allows the user time to access
the remote keypad and disarm the system.
04 Second
Entry
If at the end of normal entry (Entry 1 or 2) delay, the system has
not been disarmed, the system will start the second entry delay,
during this time the internal alarm tone will sound. If at the end of
the second entry delay the system has still not been disarmed, a
full alarm is generated.
05 Bell
Delay
When an alarm is generated, this timer is used to delay the
activation of the external sounder and strobe.
06 Bell
Duration
When an alarm is generated, this timer is used to control the
active duration of the external sounder and strobe.
07 Comms
Delay
When an alarm is generated, this timer is used to delay the
activation of the on-board communicator.
Area Arming Modes
This set of options control how the selected area is armed for
both the “Away” and “Stay” arming mode.
Locations:
2131
- Area 1 Away Arm Mode.
2231
- Area 2 Away Arm Mode.
2331
- Area 3 Away Arm Mode.
2431
- Area 4 Away Arm Mode.
2531
- Area 5 Away Arm Mode.
2132
- Area 1 Stay Arm Mode.
2232
- Area 2 Stay Arm Mode.
2332
- Area 3 Stay Arm Mode.
2432
- Area 4 Stay Arm Mode.
2532
- Area 5 Stay Arm Mode.
Entry Mode:
Bit Toggle Selection (see page 17).
0 Final
Exit
When the exit mode is started, the selected area will only arm
after the activation of a Final Exit 1 or Final Exit 2 zone type, e.g.,
after the front door is opened the closed.
1 Timed
Exit
When the exit mode is started, the selected area will arm after the
Exit Delay timer has expired.
2 Exit
Terminator
When the exit mode is started, the selected area will only arm
after activation of a Final Exit 1 or Final Exit 2 zone type, followed
by the activation of an Exit terminator zone, e.g., after the front
door is opened the closed and the push to set button has been
pressed.
3 Deferred
When the exit mode is started, the selected area will arm after the
Exit Delay timer has expired. However, if a zone off the exit route
is activated during this period, the Exit Delay timer is suspended
whilst the zone is active.
Area Configuration Options 1
This first set of configuration options controls the operation of
each area.
Locations:
2141
- Area 1 Configuration Options 1.
2241
- Area 2 Configuration Options 1.
2341
- Area 3 Configuration Options 1.
2441
- Area 4 Configuration Options 1.
2541
- Area 5 Configuration Options 1.
Entry Mode:
Bit Toggle Selection (see page 17).
1
Arming with AC off
On: The selected area can be armed when the mains supply is
switched off.
Off: The selected area cannot be armed when the mains supply
is switched off.
2
Arming with ATS Fault
On: The selected area can be armed with an Alarm Transmission
Fault (telephone line fault).
Off: The selected area cannot be armed when the mains supply
is switched off.
3
Auto Stay Arm
On: The selected area automatically performs a Stay Arm, if the
user does not activate a Final Exit zone.
Off: The selected area will always perform an Away Arm.
4 Silent
Exit
On: The selected area exit tone remains silent during exit mode.
Off: The selected area exit tone is generated during exit mode.
5
Local Exit Tone
On: If the exit tone is enabled, the exit tone is only generated
from the remote keypad that was used arm the selected
area.
Off: If the exit tone is enabled, the exit tone is generated from all
devices assigned to selected area.
6
Anti-Masking when Armed
On: Anti-Masking faults are only monitored when the selected
area is armed.
Off: Anti-Masking faults are monitored at all times for the
selected area.