Eclipse EC-P50 Installation Manual - page 27
P0016-LI-03.01
27
6
Repeat every 15 Minutes
On: The voice message repeats every 15 minutes until the
associated “Link Control” is no longer active.
Off: The voice message plays once.
7
Repeat every 30 Minutes
On: The voice message repeats every 30 minutes until the
associated “Link Control” is no longer active.
Off: The voice message plays once.
8
Repeat every 60 Minutes
On: The voice message repeats every 60 minutes until the
associated “Link Control” is no longer active.
Off: The voice message plays once.
Options 2 to 8 can be added together to create
combined timings, e.g., if option 3 and 4 are on the
voice message will repeat every 1 minute and 30
seconds.
System Links
Each system output can be assigned a “Link” number, which in
turn is used to control the “Link Control” output types, for details
on link control, see page 32.
Locations:
3901
to
3950
System Outputs 01 to 50: Link.
Entry Mode:
Number Entry (see page 18).
The table below shows the system output types and their
corresponding number 01 to 50. For details of each system
output function, please see page 31.
System Link Types
01 = AC Fault
02 = ATS Fault
03 = System Open
04 = System Armed
05 = System Part Armed
06 = System Armed/Alarm
07 = Bell
08 = Strobe
09 = Intruder Alarm
10 = Confirmed Alarm
11 = Alarm Abort
12 = Fire Alarm
13 = PA Alarm
14 = Duress Alarm
15 = 24hr Alarm
16 = Medical Alarm
17 = Tamper Alarm
18 = Ready for Arming
19 = Trouble
20 = Alert
21 = Bypass
22 = In Walk Test
23 = Flash 1 Second
24 = User Test Active
25 = PSTN Fault
26 = PSTN Off-Hook
27 = PSTN Ringing
28 = Battery Fault
29 = Control Panel Box Tamper
30 = Bell Tamper
31 = Engineer on Site
32 = Detector Reset
33 = Switched 12V
34 = System Low Volts
35 = Exit Mode
36 = Entry Mode
37 = Second Entry Mode
38 = General Alarm
39 = Auxiliary
40 = Warning
41 = Keypads Locked
42 = Output Fault
43 = Engineer Reset Required
44 = Device Fault
45 = Service Required
46 = Cleaner Bypassed
47 = 2-Wire Smoke
48 = 2-Wire Smoke Alarm
49 = 2-Wire Smoke Fault
50 = Door Access
51 = Alarm Test
52 = Panel AC On
53 = Reset Active
54 = Arming Failed
55 = Confirm Device
4. Keypad Configuration
This section covers programming of the remote keypads.
Keypad Options 1
This first set of options controls how the selected keypad onboard
keys and tamper function.
Locations:
4111
to
4114
Keypads 1 to 4: Options 2.
Entry Mode:
Bit Toggle Selection (see page 17).
1
Fire Activation from keys 1 and 3
On: Pressing keys 1 and 3 on the selected keypad at the same
time will generate a fire alarm event.
Off: The selected keypad cannot generate fire alarm events.
2
Medical Activation from keys 4 and 6
On: Pressing keys 4 and 6 on the selected keypad at the same
time will generate a medical alarm event.
Off: The selected keypad cannot generate medical alarm events.
3
PA Activation from keys 7 and 9
On: Pressing keys 7 and 9 on the selected keypad at the same
time will generate a panic alarm (PA) event.
Off: The selected keypad cannot generate panic alarm events.
4 Silent
Keypad
PA
On: If option 3 is enabled the selected keypad will generate a
silent panic alarm event.
Off: If option 3 is enabled the selected keypad will generate an
audible panic alarm event.
5
Quick Away Arm Enabled
On: The away arm mode can be carried out from the selected
keypad by simply pressing key.
Off: The user passcode must be entered at the selected keypad
before the away arm mode can be selected.
6
Quick Stay Arm Enabled
On: The stay arm mode can be carried out from the selected
keypad by simply pressing key.
Off: The user passcode must be entered at the selected keypad
before the stay arm mode can be selected.
7
Quick Bypass Enabled
On: The zone bypass feature can be invoked at the selected
keypad by simply pressing key.
Off: The user passcode must be entered at the selected keypad
before the bypass feature can be selected.
8
Keypad Tamper Enabled
On: The lid tamper on the selected keypad is monitored.
Off: The lid tamper on the selected keypad is not monitored.
Keypad Options 2
This second set of options controls how the selected keypad
functions when invalid keys are pressed (code tamper).
Locations:
4121
to
4126
Keypads 1 to 6: Options 2.
Entry Mode:
Bit Toggle Selection (see page 17).
1
Enable Code Tamper
On: Entering 15 or more invalid key presses on the selected
keypad will generate a code tamper event.
Off: The selected keypad cannot generate code tamper events.